Volt meter fluke model 87 or equivalent – System Sensor D4120W User Manual

Page 4

Advertising
background image

[7.2] LoW fLoW air fLoW TeST uSing dWYer SerieS 607
differenTiaL PreSSure TranSmiTTer
Verify the air speed of the duct using an anemometer. Air speed must be at
least 100 FPM. Wire the Dwyer transmitter as shown in Figure 5. Connect the
leads of the meter to either side of the 1000Ω resistor. Allow unit to warm up
for 15 seconds. With both HIGH and LOW pressure ports open to ambient air,
measure and record the voltage drop across the 1000Ω resistor (measurement
1), 4.00 volts is typical. Using flexible tubing and rubber stoppers, connect the
HIGH side of the transmitter to the sampling tube of the duct smoke detec-
tor housing, and the LOW side of the transmitter to the exhaust tube of the
duct smoke detector housing. Measure and record the voltage drop across the
1000Ω resistor (measurement 2). Subtract the voltage recorded in measure-
ment 1 from the voltage recorded in measurement 2. If the difference is greater
than 0.15 volts, there is enough air flow through the duct smoke detector for
proper operation.

[8] fieLd Wiring inSTaLLaTion guideLineS
All wiring must be installed in compliance with the National Electrical Code
and the local codes having jurisdiction. Proper wire gauges should be used.
The conductors used to connect smoke detectors to control panels and acces-
sory devices should be color-coded to prevent wiring mistakes. Improper con-
nections can prevent a system from responding properly in the event of a fire.

For signal wiring, (wiring between interconnected detectors or from detectors
to auxiliary devices), it is recommended that single conductor wire be no
smaller than 18 gauge.

Smoke detectors and alarm system control panels have specifications for al-
lowable loop resistance. Consult the control panel manufacturer’s specifica-
tions for the total loop resistance allowed for the particular control panel being
used before wiring the detector loop.
[8.1] Wiring inSTrucTionS
The D4120W detector is designed for easy wiring. The housing provides a
terminal strip with clamping plates. The D4S housing provides 4 wiring ter-
minals with clamping plates. Wiring connections are made by sliding the bare
end of the wire under the plate, and tightening the clamping plate screw. See
Figure 7 on page 5 for system wiring.
[8.2] SenSor 2 inSTaLLaTion/Wiring
The power board is capable of controlling a second housed sensor. The second
sensor, model D4S (NOT available in Type 4 enclosure), can be wired to the
power board per the following:

1. Connect wires to the four wire terminals in the corner of the D4S sensor

housing designated as Tamper (Y,Y), +R, and –B. Route wires through the
conduit openings in the sensor housing and D4120W power board housing.

2. Connect the opposing ends of the wires to the terminal connections

marked “Sensor 2” on the Power Board. See Figure 6 for reference. En-
sure that wires are connected to the appropriate terminal locations. A
No. 0 or 1 phillips screwdriver should be used for terminal connection.
The tamper terminals are not polarity sensitive.

3. Adjust the middle dipswitch on the power board to indicate (2) sensors

as shown in Figure 6.

4. The D4S can only be used with new InnovairFlex models and is not com-

patible with previously sold detectors.

HIGH

LOW

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

TO SAMPLING TUBE

TO EXHAUST TUBE

DIFFERENTIAL

PRESSURE

TRANSMITTER

MODEL #607-01

15 TO 36

VDC SUPPLY

1000 OHM 5%

1 WATT RESISTOR

VOLT METER FLUKE

MODEL 87 OR

EQUIVALENT

+

figure 5. Procedure for VerifYing air fLoW LeSS Than 500 fPm:

H0163-01

SS-300-010

4 I56-3046-004R

FIELD SELECTABLE

DIP SWITCHES

TEST/RESET

BUTTON

POWER

BOARD LED 2

SENSOR

LEDs

GROUND

SCREW

SENSOR #1

TERMINALS

D4120

CO-LOCATED

WIRING TERMINALS

24V

AC
/DC
, 10

24V

AC
/DC
, 9

AU
X OUT +,

19

AU
X OUT -,

20

INT/

AU
X-

, 1

INT+

, 12

ALARM,

15

R

TEST

, 11

R RESET

, 2

AC
C

-

AC
C

+

120 VAC

B

-

R

+

Y

Y

B

-

R

+

Y

Y

TAMPER

TAMPER

SENSOR 1

SENSOR 2

OFF/ON

TRBL SHUTDN

1/2 SENSORS

7/0 MIN

TMPR DEL

AY

7,

NO

18
, C

AUX B

8,

NC

17
, NO

AUX A

6,

C

16
, NC

14
, N0

3,

C

13
, NC

5,

NO

SUP

ALARM

4,

C

D4S

SENSOR ONLY

(NOT AVAILABLE IN

TYPE 4 ENCLOSURE)

SENSOR #2

TERMINALS

TAMPER

Y Y R B

Y Y R B

+ –

TAMPER

+ –

SENSOR 2

D4120

D4S

POWER

BOARD LED 1

120

VAC INPUT

24 VAC/

DC INPUT

24V AC/DC, 10

24V AC/DC, 9

AUX OUT +, 19

AUX OUT -, 20

INT/AUX-, 1

INT+, 12

ALARM, 15

R TEST, 11

R RESET, 2

ACC -

ACC +

7, NO

18, C

8, NC

17, NO

6, C

16, NC

14, N0

3, C

13, NC

5, NO

4, C

H0557-17

figure 6. oPTionaL SenSor 2 configuraTion and Wiring:

Advertising