for proper operation.
Figure 8. Procedure for verifying air flow:
DIFFERENTIAL
PRESSURE
TRANSMITTER
MODEL #607-01
HIGH
LOW
TO SAMPLING TUBE
TO EXHAUST TUBE
VOLT METER
FLUKE MODEL 87
OR EQUIVALENT
1000 OHM 5% 1 WATT RESISTOR
9 VOLT
BATTERY
9 VOLT
BATTERY
9 VOLT
BATTERY
15 TO 36VDC
SUPPLY
H0163-01
[9.1.5] Filter Replacement
The filters do not substantially affect smoke performance
even when up to 90% of the filter is clogged. Quarterly
visual inspection usually suffices to determine whether the
filters should be replaced because only a high percentage
of contamination affects performance. If further testing is
required, compare differential pressure readings with and
without the filters installed. If the difference exceeds 10%
replace the filters. In no case should the pressure differen-
tial fall below 0.0015 inches of water.
[9.2] Standby, Alarm, And Sensitivity Tests
[9.2.1] Standby And Trouble
Standby — If the system control panel is programmed,
look for the presence of the flashing LEDs through
the transparent housing cover. The LED will
flash with each communication.
Trouble — If the detector LEDs do not flash, then the de-
tector lacks power (check wiring, panel pro-
gramming, or power supply), the detector
board is missing (replace), or the unit is defec-
tive (return for repair).
Test —
The trouble condition can be caused intention-
ally to verify correct operation of the system.
Remove the detector board to cause a trouble
condition locally and at the system control
panel.
Figure 9. Wiring Diagram for DH200PL Duct Smoke Detector using a UL listed control panel:
TEST
RA400Z
RT
S451
KEY
COMMON
COM(+
)
COM(–)
TEST
RA400Z
RT
S451
KEY
COMMON
COM(+
)
COM(–)
+
–
COM
(+)
COM
(–
)
COM (+)
COM
(–
)
COMMUNICATION
LINE
UL LISTED CONTROL
PANEL
1ST DETECTOR
IN LOOP
2ND DETECTOR
IN LOOP
H0105-00
TEST
RA400Z
RTS451 KEY
COMMON
COM(+)
COM(-)
RA400Z
COMMON
DH200PL
RTS451/RTS451KEY
TEST
RTS451 KEY
COM(+)
COM(-)
4
5
6
1
2
3
FIELD INSTALLED
JUMPER
COMMON TEST
LED
RESET
FOR RTS451, TERMINAL 3 IS NOT USED.
(RTS451 DOES NOT HAVE A TERMINAL 6.)
FOR RTS451KEY, TERMINALS 3 AND 6
ARE NOT USED.
TEST
RA400Z
RTS451 KEY
COMMON
COM(+)
COM(-)
RA400Z
COMMON
DH200PL
+
RA400Z
H0458-00
H0457-00