Operation, Mounting, Start-up instructions – TREND PN-VPC User Manual

Page 2: Disposal, Pn-vpc, Data sheet

Advertising
background image

PN-VPC

Data Sheet

OPERATION

The input signal 2...10 V is fed into a voltage to current
converter in the PN-VPC.
The current through the coil produces a magnetic force on
the flapper. This force is balanced by the feedback force
developed by the nozzles pressure on the opposite side of
the flapper.
When the magnetic force on the flapper changes due to a
change in current, the position of the flapper over the
nozzle changes, and a new pressure is established. This
pressure is used to pilot the pneumatic amplifier, which
converts the low capacity pilot pressure to a high capacity
branch line. The operation span is fixed and the startpoint
of the output signal is factory calibrated.
Both transducers are compensated to eliminate ambient
temperature influence. The transducers are protected by a
rigid plastic cover.

38

diameter

4.1

4.5

78

13.5

7

47

51.5

62

Fig. 1. PN-VPC dimensions (in mm)

MOUNTING

Wall mounting with two screws 4 mm diameter (see Fig. 1).
Rail mounting using the European Standard Rail 35 x 7.5
(EN 50022) (see Fig. 2).
Mount the transducer in the vertical position ONLY with a
maximum of 5 angular degree tolerance to the
perpendicular line (see Fig. 1).

1. For test or indication gauge

2. Additional length to dismount from rail

Fig. 2. Mounting

START-UP INSTRUCTIONS

Before starting up the system, the following checks should
be made on the transducer:
1. Check that main line pressure is available and input
voltage is at maximum i.e. 12 Vdc.
2. Check that output pressure is at minimum i.e 120 kPa
(1.2 bar).
3a. If the output pressure is within the transducer rating, the
system can be started up.
3b. If not, short out the contact pins with a screwdriver.
When this is done, the sound of discharging air should be
heard.
4. Check for correct output pressure build-up and repeat
step 3(b) if transducer does not function correctly.

PN-VPC

BLUE

BROWN

BLACK

Y = 2...10 Vdc

24 V~

24 V

c
o
n
v
e

r
t

e

r

Fig. 3. Wiring and connections

DISPOSAL

WEEE Directive:

At the end of their useful life the packaging
and product should be disposed of by a suitable
recycling centre.

Do not dispose of with normal household waste.
Do not burn.

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route du Bois 37,Switzerland by its Authorized Representative

.


Trend Control Systems Ltd reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to
notify any person of such revisions or changes.


Trend Control Systems Limited
P.O. Box 34 Horsham, West Sussex, RH12 2YF, UK. Tel: +44 (0)1403 211888, Fax: +44 (0)1403 241608, www.trend-controls.com

2

PN-VPC Data Sheet TA200855 Issue 1/B 28/03/07

EN0B-0505GE51 R0307B

Advertising