TREND T_PO User Manual
Page 2

T/PO
Installation Instructions
T/PO Installation Instructions TG100241A Issue 4/B 14/02/07
2
Remove Lid
Installation
(continued)
4
a
b
Wire to Controller
7
Insert Cable
6
either use M20 flexible conduit
or use M16 cable gland
Lift Board
5
IQ1xx, IQ2xx
polarity independent
Sensor
24 Vdc
IN
Terminate screen at IQ end only
Analogue input
channel linked
for current (I)
I
IQ system TP/I/22/HF/200
(Belden 8761) cable
recommended.
IQ3
Sensor
0 (0 V)
N (in)
Terminal size 0.5 to 2.5 mm
2
(14 to 20 AWG)
Note that if connecting to an IQ22x controller (including /ADL or /OC), do not connect directly to
C (+24V), instead connect to AUX+ (+24V).
+ (24 V)
Caution: This unit contains static
sensitive devices. Suitable
anti-static precautions
should be taken throughtout
the operation to prevent
damage to the units. BS EN100015/1
Basic Specification: protection of
electrostatic sensitive devices.