NETB/LINC Installation Instructions TG200632 Issue 1/C 15/11/06

NETB/LINC

Installation Instructions

Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Ecublens, Route
du Bois 37,Switzerland by its Authorized Representative, Trend Control Systems Limited.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content
hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems Limited

P.O. Box 34, Horsham, West Sussex, RH12 2YF, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trend-controls.com

Trend Control Systems USA

6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel: (425)897-3900, Fax: (425)869-8445 www.trend-controls.com

19

Check LINC Operation

If LonWorks Internetwork (LINC address <100)

If Internetwork LonWorks Extension (LINC address =>100)

LINC

LINC

Lan

LonWorks

IQL

LONC

or

or

LINC

LINC

Lan

LonWorks

IQL

LONC

I/N

or

or

terse text comms

terse text comms

3.2 Installation - Configuration

(Continued)

4 Replacing the Fuse

Switch off

1

O

I

Open Panel

2

NETB/LINC/FTT/24 only for
UL rating

Remove Side Covers

3

slide out

press down catches

WARNING:
Removal of the cover
exposes dangerous voltages.

417-IEC-5036

undo screws

5 Disposal

WEEE Directive :

At the end of their useful life the packaging,
and product, should be disposed of by a
suitable recycling centre.

Do not dispose of with normal household waste.
Do not burn.

The unit is UL rated as 'UL916,
accessory to open energy
management equipment.'

4

Replace Fuse

Fuse: 20 mm, (T) anti-surge
230 Vac: 50 mA
24 Vac: 630 mA

S C N

S C N

T -

T +

R -

R +

T -

T +

R -

R +

N

E

L

~

2 3 0 V a c

T h i s u n i t m u s t b e e a r t h e d

LO

N

J 1 8

J 8

J 7

J 6

J 1 6

F S I

L o n A
L o n B

S C N

L o n A
L o n B

S C N

TR

E

N

D

N

E

TW

O

R

K

5 0 / 6 0 H z

1 8 V A

S

U

P

P

LY

F

U

S

E

5

0

m

A

(T

)

L I N C

Replace Side Covers

5

slide in

replace screws

Switch On

7

O

I

6

Close Panel

NETB/LINC/FTT/24 only
for UL rating

The unit is UL
rated as
' U L 9 1 6 ,
accessory to
open energy
management
equipment.'

Advertising