REV 5 TTRA VERSION 12.x SOFTWARE MANUAL

38

5. To set the test voltage, click on the “Voltage:” drop-down list and select the desired test

voltage (8 Vac, 40 Vac, or 100 Vac).

6. Enter the “H Voltage”, “H Tap”, “X Voltage”, and “X Tap” values for the first row by

clicking on each cell and then typing the value. You can also click on a cell, enter the
value, and then press the [TAB] key to move to the next cell on the right. You can also
use the up and down arrow keys to move vertically. Once the “H Voltage” and “X
Voltage” values have been entered, the calculated ratio will be displayed in the “Calc.
Ratio” column.

7. You can set the number of tests in the test plan by clicking on the “Set # of Tests”

button. The following window will be displayed:

Enter the number of tests, and then click on the “OK” button. This number will
determine the number of tests (data rows) in the blank test plan.

8. Once all information has been entered, save the test plan (see section 5.4).