25.0 Step-by-Step Turns Ratio Testing Procedures
25-1 Single-Phase Transformer Test Procedure
Table 25.1 shows the steps to test a single-phase transformer.
Table 25-1. Single-Phase Transformer Test Procedure.
STEP
DESCRIPTION
DISPLAY
ACTION
1
Initiate Transformer Test
1. TEST XFMR 04/12/00
2. SETUP 13:06:02
3. CALCULATOR
Press key 1
2
Select Single Phase
Transformer
XFMR CONFIGURATION:
1. SNGL PHS 2. dT-Y
3. Y-dT 4.dT-dT
5. Y-Y
Press key 1.
3
Select not to use
transformer name plate
voltage
XFMR NAME PLATE VLTG
1. YES
2. NO
Press key 2.
4
Start test
SINGLE PHASE XFMR
“START” TO RUN TEST
OR
“STOP” TO ABORT
Press START key
5
Display ratio, excitation
current
RATIO mA %DIFF
+1.000 0002
None