AVI HOOD ELECTRICAL REQUIREMENTS

Inputs into Junction Box

The AVI Hood system provides:

Three (3) switching outputs for HVAC dampers and dedicated units

One (1) 230 VAC, 10 Amp, variable frequency, three phase power output for the ventilation
exhaust fan.

Up to Three (3) receptacles for ovens.

One (1) 120 VAC fire alarm signal for Standard hoods, or one (1) 24 VAC fire alarm signal for
World Hoods

Outputs from Junction Box

# of Circuits

Rating

Purpose

1

208/240 VAC, 1 Phase, 60 Hz, 6 Amp

VFD Controller

up to 3

120 VAC, 1 Phase, 60 Hz, 20 Amp

Ovens

1

120 VAC, 1 Phase, 60 Hz, 1 Amp

System Power

1

230 VAC, 1 Phase, 50 Hz, 6 Amp

VFD Controller

up to 3

230 VAC, 1 Phase, 50 Hz, 10 Amp

Ovens

1

230 VAC, 1 Phase, 50 Hz, 1 Amp

System Power

Standard

World

AVI Hood Electric Utility Specifications