Wiring and connecting the ups – American Power Conversion 5000 VA User Manual

Page 4

Advertising
background image

2

Wiring and Connecting the UPS

5000

VA

XLI

MODELS

O

NLY

:

H

ARDWIRING

I

NSTRUCTIONS

• Wiring must be performed by a qualified electrician.
• Install a high magnetic 30/32 A utility circuit breaker.
• Adhere to all national and local electrical codes.
• Use #10 AWG gauge (5 mm

2

) wire.

1. Switch the utility circuit breaker OFF.
2. Remove the input access panel.
3. Remove circular knockout.


4. Run #10 AWG gauge (5 mm

2

) wire through the access panel, and connect the wires to the

terminal block (Green: Ground, Brown: Hot, Blue: Neutral). Use an appropriate strain relief (not
included).


5. Switch the utility circuit breaker ON.
6. Check line voltages.
7. Replace the access panel.

Advertising