FIGURE 2. VACUUM BREAKER WITH

OPTIONAL FLANGE


INSTALLATION

The installation of the valve is important for its
proper operation. The seat end must be oriented
upward. The valve should be installed on top of
horizontal lines or tanks and equipped with an
isolation valve. If installed in a vault, adequate
ventilation is needed to supply air to the vacuum
breaker.

The valve should be installed to a standard flat-face
flange per ANSI B16.5 or AWWA C207.

When used with an outlet flange, special flange
requirements are given in Drawing SS-1381 on page
3. The mating flange inside diameter must overlap
the valve seat to provide proper seat retention.
Outlet piping and companion flange are required to
retain the seat and disc. Remove the ring flange
and 2 bolts supplied with the vacuum breaker, and
replace with external, full-size flanged piping.






When mating the check valve with butterfly isolation
valves, the clearance between the butterfly disc and
the fully open check valve stem must be checked.

The location of the stem is also shown on the
vacuum breaker submittal drawings. 10 inch and
smaller vacuum breakers have sufficient clearance
for most butterfly valves. However, on 12 inch and
larger valves, the shaft extends beyond the flange
face and may interfere with the operation of adjacent
valves. A short run of pipe or spacer may be
needed between the vacuum breaker and the
isolation valve.

FLANGED ENDS: The flange should be mated with
flat-faced pipe flanges equipped with resilient
gaskets. When ring gaskets are used, the bolt
material shall be ASTM A307 Grade B or SAE
Grade 2 Carbon Steel. Higher strength bolts should
only be used with full-face gaskets.

INSTALLATION: Lower valve over mating flange
using slings or chains around the valve body.

Lubricate the flange bolts and insert them around
the flange. Lightly turn bolts until gaps are
eliminated. The tightening of the bolts should then
be done in graduated steps using the cross-over
tightening method. Recommended lubricated
torques for use with resilient gaskets (75 durometer)
are given in Table 1.

If leakage occurs, allow gaskets to absorb fluid and
check torque and leakage after 24 hours. Do not
exceed bolt rating or crush gasket more than 50 per
cent of its thickness.

125# FLANGE DATA

250# FLANGE DATA

Valve

Size

(in)

Bolt

Dia.

(in)

Bolt

Torque

(ft-lbs)

Valve

Size

(in)

Bolt

Dia.

(in)

Bolt

Torque

(ft-lbs)

2.5 5/8

25-75

2.5 3/4

25-75

3 5/8

25-75

3 3/4

35-75

4 5/8

30-90

4 3/4

50-150

5 3/4

30-90

5 3/4

70-150

6 3/4

30-90

6 3/4

70-150

8 3/4

40-120

8 7/8

90-200

10 7/8

45-150

10 1

110-300

12 7/8

65-200

12 1

1/8

160-450

14 1

80-250

14 1

1/8

140-450

16 1

90-300

16 1

1/4

180-600

18 1

1/8

100-350

18 1

1/4

190-600

20 1

1/8

120-450

20 1

1/4

220-600

24 1

1/4

150-500

24 1

1/2

350-900

30 1

1/4

180-600

30 1

3/4

500-1500

36 1

1/2

250-750

36 2

700-2000

42 1

1/2

300-900

42 2

800-2500

TABLE 1. FLANGE BOLT TORQUES

WARNING: Vacuum Breakers with Flanged

Outlets must have outlet piping
installed or damage may occur.