HMI5000L Installation Guide

1010-1018 Rev 01 www.maplesystems.com

frequency noise present, we also recommend using a resistor (~1 MΩ)

and capacitor (~4700 pF) in parallel to clean earth ground on the DC

output of the power supply.

Do not use the power supply used to provide power to the HMI to power

switching relays, solenoids, or other active devices.

Figure 3: Power Line Filter Connection

Cable Routing and Noise Immunity

Follow these guidelines when routing cables to the HMI:

Always route the HMI communication cable and the power cable

away from any AC voltage or rapidly switching DC control

lines.

Never bundle the HMI cables together with 120VAC power

wires or with relay wiring.

Try to keep at least 8 inches (20 cm) of separation between the

HMI cables and other power wiring. If voltages greater than

120VAC are used in the system, greater separation is required.

If the HMI cables must come near AC wiring, make sure they

cross at 90 degrees.