EZwarePlus Programming Manual

107

1010-1015, Rev. 03

12. Default station no. use station no. variable: Enables using a Local Word (where LW10000-LW10015

corresponds to var0-var15) to define the station number. By using the var syntax in the address field
(e.g., var0#100), the station number can be changed at runtime by changing the value in the
corresponding Local Word.

13. Use broadcast command: When enabled, causes the HMI to not expect a response from the station

number specified by the Broadcast station no. field.

14. Interval of block pack (words): Determines how many words are read from the PLC in one

communication cycle. For more information on this feature, select Help> Help Topics in EZwarePlus
and select Miscellaneous > Optimizing the Update Rate With PLC Block Pack.

15. Max. read-command size (words): The maximum data size to be read from a device at one time.

 The Interval of block pack (words) setting must be less than this setting.

16. Max. write-command size (words): The maximum data size to be written to a device at one time.

17. Refer to chapter xx for details on the Address Mapping Table and Modbus Gateway.

18. Click OK.