Proface LT3300 - 5.7 All-in-One HMI" User Manual

Page 5

Advertising
background image

5

„ DIO Interface (Connector)

• When preparing the cable to connect the wiring, check the pin numbers inscribed on

the DIO Connector.

• Parenthesized signal names ( ) indicate when Pulse output (PLS

∗), PWM output (PWM∗), or

Counter Input (CT

∗) are used.

Applicable connector

2-1871940-9 <Tyco Electronics AMP.>

CA7-DIOCN5-01 <Pro-face>

Pin Arrangement

Pin No.

Signal Name

Pin No.

Signal Name

A1

IN1

B1

IN0 (CT0)

A2

IN3

B2

IN2 (CT1)

A3

IN5

B3

IN4 (CT2)

A4

IN7

B4

IN6 (CT3)

A5

IN9

B5

IN8

A6

IN11

B6

IN10

A7

IN13

B7

IN12

A8

IN15

B8

IN14

A9

NC

B9

COM

A10

Sink: NC

B10

Sink: +24V

Source: +24V

Source: +24V

A11

Sink: 0V

B11

Sink: 0V

Source: NC

Source: 0V

A12

OUT1

(PLS1, PWM1)

B12

OUT0

(PLS0, PWM0)

A13

OUT3

(PLS3, PWM3)

B13

OUT2

(PLS2, PWM2)

A14

OUT5

B14

OUT4

A15

OUT7

B15

OUT6

A16

OUT9

B16

OUT8

A17

OUT11

B17

OUT10

A18

OUT13

B18

OUT12

A19

OUT15

B19

OUT14

(Cable connection side)

A1

B1

B19

A19

Advertising