RAS Interface

• Be sure to use only the rated voltage

level when using pin #1 (+12V) for
external power output. Failure to do so
can lead to a unit malfunction or acci-
dent.

• For the circuit diagram, refer to “PL3000

Series Reference Manual”.

Installations

• Before installing the PL unit on the

panel, detach the control box from the
front module to configure the settings
of the internal switches.

1.

Installation Requirements

• For easier maintenance, operation, and

improved ventilation, be sure to install the
PL at least 50mm [1.97 in.] away from
adjacent structures and other equipment.
For the face to which the cable is con-
nected, however, a space of 120 mm [4.72
in.] or more is necessary for cable curve.

• Be sure that the surrounding air temperature

and the ambient humidity are within their
specified ranges.
When installing the PL on the panel of a
cabinet or enclosure, “Surrounding air tem-
perature” indicates both the panel face and
cabinet or enclosure’s internal temperature.

• Be sure that heat from surrounding equip-

ment does not cause the PL to exceed its
standard operating temperature.

2.

PL Installation

(1) Create a Panel Cut using the dimensions

in the following table. Also, determine
the panel thickness according to the panel
thickness range with due consideration of
panel strength.

Interfit Bracket #4-40(UNC)

Pin # Signal Name

Description

1

+12V

Output Current:
100mA or less
Output Voltage:
12V±5%

2

DOUT0(+)

Data out 0(+)

3

DOUT1(+)

Data out 1(+)

4

DIN0(+)

Data in 0(+)

5

DIN1(+)

Data in 1(+)

*1

*1 Can be used as reset input.

6

GND

Ground

7

DOUT0(-)

Data out 0(-)

8

DOUT1(-)

Data out 1(-)

9

DINCOM

Data in ground
common

SEE

Installation/uninstallation of the
front module and the control
box,
Internal Switches

Unit:mm[in.]

120
[4.72]

50
[1.97]

50
[1.97]

50
[1.97]

50

[1.97]
50

[1.97]

50
[1.97]

Panel face

Cabinet
interior

30

[1.18]

30
[1.18]

unit:mm[in.]

50
[1.97]

PL

X

Unit:mm[in.]

Y

r

≤ 3[0.12]

Panel
thickness