Connecting the Power Supply

•

If the power supply voltage exceeds the FP unit’s spec-

ified range, connect a constant voltage transformer.

•

For between the line and ground or between the lines,

select a power supply that is low in noise. If there is an

excess amount of noise, connect an insulating trans-

former.

•

When supplying power to the FP unit, please separate

the input/output and operation unit lines, as shown.

•

To increase the noise resistance quality of the power

cable, simply twist each power wire before attaching

the Ring Terminal.

•

The power supply cable must not be bundled or posi-

tioned close to main circuit lines (high voltage, high

current), or input/output signal lines.

•

Connect a lightning surge absorber, as shown in the

diagram, to deal with power surges.

•

To avoid excess noise, make the power cable as short

as possible.

•

The temperature rating of field installed conductors:

75

o

C only.

SEE

4 Specifications (page4-1)

• Use the constant voltage

transformer and the insulating

transformer with capacities of the

rated value or more.

• Be sure to ground the surge

absorber (E1) separately from the

FP unit (E2).

• Select a surge absorber that has a

maximum circuit voltage greater

than the power supply’s peak

voltage.

Main

Power

FP

Power

T1

T2

Main Circuit Power

FP Unit

Input/Output

Unit

Input/Output

Unit

Operation

Unit

E1

lightningsurge
absorber

FG

FP Unit

E2

FP Unit

Input/Output

Unit

Main

Power

FP

Power

Input/Output

Power

Motor

Input/Output

Power

Twisted-pair cord

Constant

Voltage

Transformer

Insulating

Transformer

Twisted-pair cord

FP Unit

FP Unit

FG

FG