Troubleshooting

PROBLEM

Cause / Correction

No power available to heater

Check disconnect switch to ensure it is in the "ON" position

and that fuses are not blown. Replace fuses if they are blown

Fuses blowing

Check heater electrical rating. Applied voltage may be wrong

Check fuse rating. Fuses should be at least 25% more than full
load amperage.
Disconnect heater power source. Check the heater resistance
to ground. This should be no less than 1 Megohm. Refer to
Megohm checking.

Not enough power

Check line voltage to ensure it is within specification

Check full line current if voltage is correct. If line current is lower,
the heater may be wired wrong or has open elements

Fluid not heating to desired

Not enough Kw

temperature

Too much heat loss

High limit tripping / alarm

Not enough fluid flow

Too much Kw
Line voltage higher than designed / allowable

Preventative Maintenance

CAUTION: HAZARD OF ELECTRIC SHOCK. TURN ALL POWER TO HEATER OFF, USE
APPROPRIATE DISCONNECT LOCKOUTS AND ALLOW SYSTEM/HEATER TO COOL BEFORE
PERFORMING ANY MAINTENANCE

!


Check line connections to make sure they are tight, free of oxide build-up, and that no dust or dirt build-up is
present. Retighten to 20 in-lbs as necessary.

Check enclosure (inside) for rust, dirt or dust. Remove rust if present, with steel wool (or equal) and
thoroughly blow clean with dry, oil-free air.

If enclosure is moisture resistant, check condition of cover gasket. A replacement can be obtained from the
factory.

Liquid immersed units should be removed from tank and checked periodically for scale build-up. Clean as
required. Scale can cause high sheath temperature and result in inefficiency and shortened life.

Thermal cycling may cause sealed joints to relax causing a leak. Tightening of heater plug should stop leak.

Replacement Parts

Reference the Flange Heater part number on the nameplate when ordering replacement parts.
Recommended spare parts would be : a Flange Heater and thermostat (if supplied).

Contact your local Watlow distributor for ordering replacement parts. Check the Yellow Pages under
"Electrical Heating Elements" in the largest industrial area nearest you.