Toxalert GVU-2R User Manual

Page 3

Advertising
background image

TABLE 1
AWG

DO NOT EXCEED

#22 Wire

500 Ft. Sensor to Controller

#20 Wire

800 Ft. Sensor to Controller

#18 Wire

1300 Ft. Sensor to Controller

#16 Wire

2000 Ft. Sensor to Controller

TABLE 2

WIRING CONNECTIONS

GVU-CO

CONTROL UNITS

SENSOR

GVU-1

GVU-3

1

TB2-7

TB1-A7,B7,C7

2*

TB2-6

TB1-A6,B6,C6

4

TB2-1

TB1-A1,B1,C1

5

TB2-4

TB1-A4,B4,C4

**

TB2-5

TB1-A5,B5,C5

* Optional-power to sensor indication.
** Shield of cable (if used) should be connected at control unit only.
Make sure sensor end is taped and isolated from terminals or metal.

GVU SERIES PRODUCTS:

CONTROLLERS

GVU-1

Control unit for use with one sensor

GVU-3

Control unit for use with one to three remote sensors

GVU-6

Control unit for use with one to six remote sensors

GVU-12

Control unit for use with one to twelve remote sensors

GVU-18

Control unit for use with one to eighteen remote sensors

REMOTE SENSORS –

GVU-CO Remote carbon monoxide sensor

GVU–NO

2

Remote nitrogen dioxide sensor

GVU-CO

2

Remote CO sensor

GVU–VOC Remote smoke/air quality sensor

GVU-CO revised 4/14

TOXALERT INTERNATIONAL, INC., P.O. BOX 159, MOUND, MINNESOTA 55364 (952) 472-4541 FAX (952) 472-4960

Visit our website at www. toxalert. com

NOTE: Refer to Figure 2 and Tables 1 and 2. Use

shielded cable to interconnect sensor and

control unit if metal conduit is not used, or

if conduit also contains AC wiring.

1.) Measure distance between sensing unit and

control unit and select proper wire or larger

wire from Table 1.

2.) Run wiring between control and sensing unit

and into enclosure through access holes.

Connect wires from terminal blocks in sensing

unit to control unit per Table 2 and GVU series

control unit data sheet.

3.) Verify all wiring connections and turn power

on to sensor.

3. BURN -IN:

Burn-in period allows sensor to stabilize before

proceeding with alarm setting procedure.

1.) Verify sensor has power, sensor LED should

be flashing green or red.

2.) Allow systems to burn-in for a minimum of

72 hours with power turned on to sensor.

3.) When 72 hours have elapsed, proceed with

system checkout according to GVU series

control unit data sheet.

Sensor is factory calibrated to 50 ppm CO and

requires no field calibration for installation.

If the GVU-CO indicator LED is not flashing,

this indicates sensor failure, please contact your

local representative or TOXALERT International.