15 ° c when /he is specified, Safe area hazardous area, Terminator – Yokogawa EJA115 User Manual

Page 5

Advertising
background image

( IV ) for /KN26

c. ATEX Type of Protection “n”

Model EJA Series differential, gauge, and absolute
pressure transmitters with optional code /KN26.

WARNING

When using a power supply not having a
nonincendive circuit, please pay attention not to
ignite in the surrounding flammable atmosphere.
In such a case, we recommend using wiring
metal conduit in order to prevent the ignition.

WARNING

• Electrostatic charge may cause an explosion

hazard. Avoid any action that cause the gen-
eration of electrostatic charge, such as rubbing
with a dry cloth on coating face of the product.

• Applicable standard: EN 60079-0:2009, EN60079-

15:2005

• Type of Protection and Marking Code:

Ex nL IIC T4 Gc

• Group: II
• Category: 3G
• Ambient Temperature: –30* to 60

°

C

*–15

°

C when /HE is specified

• Ambient humidity: 0 to 100%RH (No condensation)
• Enclosure: IP67

Note 1. Electrical Data

Ui = 32 Vdc
Ci = 3.52 nF
Li = 0

µ

H

Note 2. Installation

• All wiring shall comply with local installation

requirements. (refer to the installation diagram)

Safe Area

Hazardous Area

F0208.EPS

Terminator

Terminator

Field Instruments

EJA

Pressure

Transmitter

Field Instruments

Associated

Apparatus

ϩ

Ϫ

ϩ

Ϫ

ϩ

Ϫ

Vmax = 32 Vdc
Ci = 3.52 nF
Li = 0

H

Note 3. Maintenance and Repair

• The instrument modification or parts replacement by

other than authorized representative of Yokogawa
Electric Corporation is prohibited and will void
Type of Protection “n”.

(V)

Tag plate for flameproof type

Tag plate for flameproof, intrinsically safe type,

type n protection, and Dust (for /KU22)

F0298.EPS

D

T65

Њ

C (Tamb.: 40

Њ

C), T85

Њ

C (Tamb.: 60

Њ

C),and T105

Њ

C (Tamb.: 80

Њ

C)

AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING. WHEN THE
AMBIENT TEMP.

Ն

70

Њ

C, USE THE HEAT-RESISTING CABLES

Ն

90

Њ

C. SEE USER'S

MANUAL BEFORE USE. POTENTIAL ELECTROSTATIC CHARGING HAZARD.

SEE USER'S
MANUAL

Tamb.

Ϫ

30(

Ϫ

15) TO 60

Њ

C

TEMP.CLASS/MAX SURFACE TEMP. T6/T85

Њ

C T5/T100

Њ

C T4/T120

Њ

C

WARNING

D

, Ex tD A21 IP6X T85

Њ

C,T100

Њ

C,T120

Њ

C

ENCLOSURE:IP67

Tamb.

Ϫ

40(

Ϫ

15) TO

KU22

Tamb.

Ϫ

40(

Ϫ

15) TO 75

Њ

C(T6 and T4)

AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP.

Ն

70

Њ

C, USE THE HEAT-RESISTING

CABLES

Ն

90

Њ

C. SEE USER'S MANUAL BEFORE USE.

Ϫ

40(

Ϫ

15) TO 80

Њ

C(T5)

CAUTION

KF21

Tag plate for flameproof, intrinsically safe type,

type n protection, and Dust (for /KU21)

D

T65

Њ

C (Tamb.: 40

Њ

C), T85

Њ

C (Tamb.: 60

Њ

C),and T105

Њ

C (Tamb.: 80

Њ

C)

AFTER DE-ENERGIZING, DELAY 10 MINUTES BEFORE OPENING.
WHEN THE AMBIENT TEMP.

Ն

70

Њ

C, USE THE HEAT-RESISTING

CABLES

Ն

90

Њ

C. SEE USER'S MANUAL BEFORE USE.

SEE USER'S
MANUAL

Tamb.

Ϫ

40(

Ϫ

15) TO 60

Њ

C

TEMP.CLASS/MAX SURFACE TEMP. T6/T85

Њ

C T5/T100

Њ

C T4/T120

Њ

C

CAUTION

D

, Ex tD A21 IP6X T85

Њ

C,T100

Њ

C,T120

Њ

C

ENCLOSURE:IP67

Tamb.

Ϫ

40(

Ϫ

15) TO

KU21

Gc

Advertising