Yokogawa EJA115 User Manual

Page 2

Advertising
background image

( I )

b. CENELEC ATEX (KEMA) Flameproof Type

Caution for CENELEC ATEX (KEMA) flameproof
type.

Note 1. Model EJA Series differential, gauge, and

absolute pressure transmitters with
optional code /KF21 for potentially
explosive atmospheres:

• No. KEMA 02ATEX2148
• Applicable Standard: EN60079-0:2006, EN60079-

1:2004

• Type of Protection and Marking Code: Ex d IIC

T6···T4

• Temperature Class: T6, T5, and T4
• Enclosure: IP67
• Maximum Process Temperature:

85

°

C (T6), 100

°

C (T5), and 120

°

C (T4)

• Ambient Temperature: T4 and T6; –40* to 75

°

C,

T5; –40* to 80

°

C

*–15

°

C when /HE is specified.

Note 2. Electrical Data

• Supply voltage: 42 V dc max.
• Output signal: 4 to 20 mA

Note 3. Installation

• All wiring shall comply with local installation

requirement.

• The cable entry devices shall be of a certified

flameproof type, suitable for the conditions of use.

Note 4. Operation

• Keep the “CAUTION” label to the transmitter.

CAUTION: AFTER DE-ENERGIZING,
DELAY 10 MINUTES BEFORE
OPENING. WHEN THE AMBIENT
TEMP.

м

70

°

C, USE HEAT-RESISTING

CABLES

м

90

°

C.

• Take care not to generate mechanical sparking

when accessing to the instrument and peripheral
devices in a hazardous location.

Note 5. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void KEMA Flameproof Certification.

( II )

c. CENELEC ATEX (KEMA) Intrinsically Safe

Type/CENELEC ATEX (KEMA) Flameproof
Type/CENELEC ATEX Type n

Model EJA-A Series pressure transmitters with
optional code /KU21 can be selected the type
of protection CENELEC ATEX (KEMA) Intrinsi-
cally Safe, Flameproof or CENELEC ATEX
Type n for use in hazardous locations.

Note 1. For the installation of this transmitter,

once a particular type of protection is selected,
any other type of protection cannot be used.
The installation must be in accordance with the
description about the type of protection in this
user’s manual.

Note 2. In order to avoid confusion, unnecessary

marking is crossed out on the label other than
the selected type of protection when the
transmitter is installed.

CENELEC ATEX Type of Protection “n”

WARNING

When using a power supply not having a non-
incendive circuit, please pay attention not to
ignite in the surrounding flammable atmosphere.
In such a case, we recommend using wiring
metal conduit in order to prevent the ignition.

• Applicable Standard: EN60079-15
• Referential Standard: IEC60079-0, IEC60079-11
• Type of Protection and Marking Code:

Ex nL IIC T4

• Temperature Class: T4
• Enclosure: IP67
• Process Temperature: 120

°

C max.

• Ambient Temperature: –40* to 60

°

C

*–15

°

C when /HE is specified.

Note 1. Electrical Data

Ui = 30 V
Effective internal capacitance; Ci = 22.5 nF
Effective internal inductance; Li = 730

µ

H

Note 2. Installation

• All wiring shall comply with local installation

requirements. (refer to the installation diagram)

Note 3. Maintenance and Repair

• The instrument modification or parts replacement

by other than authorized representative of
Yokogawa Electric Corporation is prohibited and
will void Type of Protection “n”.