<4. Self-diagnostics>

4-3

IM 01C25T03-01E

Indicator

BT200 display

Cause

Output operation

during error

Countermeasure

AL. 50

P. LRV

50: P ILLEG LRV

Specified value is outside of

setting range.

Holds output

immediately before

error occurred.

Check settings and

change them as needed.

AL. 51

P. URV

51: P ILLEG URV

AL. 52

P. SPN

52: P ILLEG SPAN

AL. 53

P. ADJ

53: P SPAN ADJ

Continues to operate

and output.

Adjust settings and

change them as needed.

53: P ZERO ADJ

AL. 54

SP. RNG

54: SP ILLEG LRV

Continues to operate

and output holding

static pressure in %.

Check settings and

change them as needed.

54: SP ILLEG URV
54: SP ILLEG SPAN

AL. 55

SP. ADJ

55: SP SPAN ADJ

Continues to operate

and output.

Adjust settings and

change them as needed.

55: SP ZERO ADJ

AL. 60

SC. CFG

60: SC CONFIG ERR Specified values or settings do

not meet the conditions.

Continues to operate

and output without

signal characterizing.

Check settings and

change them as needed.

AL. 79

OV. DISP

Displayed value exceeds limit. Continues to operate

and output.