Yokogawa EJA440E User Manual

Page 32

Advertising
background image

<4. Self-diagnostics>

4-3

IM 01C25T03-01E

Indicator

BT200 display

Cause

Output operation

during error

Countermeasure

AL. 50

P. LRV

50: P ILLEG LRV

Specified value is outside of

setting range.

Holds output

immediately before

error occurred.

Check settings and

change them as needed.

AL. 51

P. URV

51: P ILLEG URV

AL. 52

P. SPN

52: P ILLEG SPAN

AL. 53

P. ADJ

53: P SPAN ADJ

Continues to operate

and output.

Adjust settings and

change them as needed.

53: P ZERO ADJ

AL. 54

SP. RNG

54: SP ILLEG LRV

Continues to operate

and output holding

static pressure in %.

Check settings and

change them as needed.

54: SP ILLEG URV
54: SP ILLEG SPAN

AL. 55

SP. ADJ

55: SP SPAN ADJ

Continues to operate

and output.

Adjust settings and

change them as needed.

55: SP ZERO ADJ

AL. 60

SC. CFG

60: SC CONFIG ERR Specified values or settings do

not meet the conditions.

Continues to operate

and output without

signal characterizing.

Check settings and

change them as needed.

AL. 79

OV. DISP

—

Displayed value exceeds limit. Continues to operate

and output.