User’s manual – Yokogawa EJX440A User Manual

Page 7

Advertising
background image

User’s

Manual

DPharp

Differential Pressure and

Pressure Transmitters

Manual Change No. 12-023

Oct. 5, 2012

Please correct the information on the following manual as listed below .
IM 01C25T02-01E (12th)

Page and Item

Correct Information

P.2-10

c. ATEX Type of Protection “n”

Note 1.

Applicable Standard:

EN 60079-0:2009, EN 60079-15:2005

P.2-10

c. ATEX Type of Protection “n”

Note 2

Electrical Data

Ui=32 Vdc, Ci=3.52 nF, Li=0 μH

P.2-10

[Installation Diagram]

See the picture ( I ) in below.

P.2-11

(6) Name Plate

See the picture ( II ) in below.

( I )

Non-Hazardous

Locations

Hazardous Locations

[Installation Diagram]

F0209.ai

Terminator

Field Instruments

(Passive)

Hand-

held-

Terminal

(Zone2)

Terminator

Associated

apparatus

U

( II )

Tag plate for type n protection

F0211a.ai

WARNING

Ex nL IIC T4 Gc

ENCLOSURE IP66/IP67

Tamb. -30(-15) to 60°C

MAX. PROCESS TEMP. 120°C

Ui=32V, Ci=3.52nF, Li=0µH

POTENTIAL ELECTROSTATIC CHARTGING HAZARD - SEE USER'S MANUAL.

Advertising