2. Contents of change

(I) Transmitter Mounting (for EJA118E, EJX118A,

EJA438E, and EJX438A)

Please replace the original contents as follows when

the transmitter cannot be installed at least 600 mm
below the HP process connection.

IMPORTANT

The transmitter should be installed at least 600 mm below

the high pressure (HP) process connection to ensure a

positive head pressure of fill fluid. Pay special attention to

vacuum applications.

If it can not be installed at least 600 mm below the HP

process connection, please use the equation below:

h=

× 0.102

[mm]

(P–P0)

ds

h: Vertical height between the HP process connection

and the transmitter (mm)
h≤0: Install the transmitter at least h (mm) below the

HP process connection

h>0: Install the transmitter at most h (mm) above the

HP process connection

P: Pressure in the tank (Pa abs)
P0: Minimum working pressure limit of the transmitter (Pa

abs). See below table.

[For fill fluid code A, B, C, D, E]

Wetted parts

material code

Capillary

length

Process connection size

code

2, 8

3

4,W

SW

1 to 5m

6790

3190

6 to 10m

10030

3520

SE

1 to 5m

6790

3190

6 to 10m

10030

3520

SY

1 to 5m

3190

6 to 10m

3520

HW

1 to 5m

19150

6140

6 to 10m

8290

TW

1 to 5m

9620

3620

6 to 10m

4210

UW

1 to 5m

9540

4750

6 to 10m

6050

[For fill fluid code 1, 2, 4]

Wetted parts

material code

Capillary

length

Process connection size

code

2, 8

3

4,W

SW

1 to 5m

2570

320

6 to 10m

4680

530

SE

1 to 5m

2570

320

6 to 10m

4680

530

SY

1 to 5m

320

6 to 10m

530

HW

1 to 5m

10220

2050

6 to 10m

3450

TW

1 to 5m

4270

570

6 to 10m

960

ds: Specific gravity of fill fluid (at 25°C). See below table.

Fill fluid code A, 1, 4

B

C, 2

D

E

ds: Specific

gravity

1.07

0.94

1.09

1.90 to

1.92

1.09

(II) Capillary Fill Fluid Density Compensation (for

EJA118E, EJX118A, EJA438E, and EJX438A)

Please use the following constant value [B] of fill fluid

for the capillary fill fluid density compensation when fill
fluid code 1, 2, or 4 is specified.

Table A. Constant value [B] of fill fluid

Fill fluid code

1, 2, 4

Constant value [B] mmH

2

O

0.75

Kgf/cm

2

0.0000745

kPa

0.00745

mbar

0.07453

atm

0.000074

inH

2

O

0.02992

psi

0.00108

mmHg

0.05592