Wiring, 1 wiring precautions, 2 cables – Yokogawa AXFA11 Magnetic Flow Converter User Manual

Page 4

Advertising
background image

IM 01E20C01-01E

4. WIRING

4.

WIRING

This section describes the wiring on the converter side
only. For information relating to wiring on the
flowtube side, refer to the user’s manual of the AXF
Remote Flowtube (IM 01E20D01-01E).

WARNING

The wiring of the magnetic flowmeter must be
performed by expert engineer or skilled person-
nel. No operator shall be permitted to perform
procedures relating to wiring.

CAUTION

Once all wiring is complete, check the connec-
tions before applying power to the instrument.
Improper arrangements or wiring may cause a
unit malfunction or damage.

4.1 Wiring Precautions

Be sure to observe the following precautions when
wiring:

CAUTION

• In cases where the ambient temperature

exceeds 50

°C (122°F), use external heat-

resistant wiring with a maximum allowable
temperature of 70

°C (158°F) or above.

• Do not connect cables outdoors in wet weather

in order to prevent damage from condensation
and to protect the insulation.

• Do not splice the cable between the flowtube

terminal and the converter if it is too short.
Replace the short cable with a cable that is the
appropriate length.

• All the cable ends must be provided with round

crimp-on terminals and be securely wired.

• The signal cables must be routed in separate

steel conduit tubes 16 (JIS C 8305) or flexible
conduit tubes 15 (JIS C 8309).

• Always route the power and output signal

cables in separate steel conduit tubes, except
when the power supply voltage is 24 V and

four-core cables are used for wiring. Keep
conduits or flexible tubes watertight using
sealing tape.

• Ground the remote flowtube and the converter

separately.

• Cover each shield of the signal cable with vinyl

tube or vinyl tape to avoid contact between two
shields or between a shield and a case.

• When waterproof glands or union equipped

waterproof glands are used, avoid tightening
the glands with an excessive torque.

• Be sure to turn power off before opening the

cover.

• Before turning the power on, tighten the cover

securely.

IMPORTANT

Prepare the signal cable and the excitation cable
almost the same length. It is recommended to
lay them together closely.

4.2 Cables

(1) Dedicated Signal Cable (AXFC)

Outer jacket

10.5 (0.413")

Tape

Shield (C)

Insulation

Insulation

Shields (SA and SB)

Conductors (A and B)

F0401.EPS

Figure 4.2.1 Dedicated Signal Cable AXFC

The flow signal is transmitted via this dedicated cable.
The cable is constructed with double shielding over the
two conductors, and heat-resistant vinyl is used for the
outer jacket material.

Finished diameter:

10.5 mm (0.413")

Maximum length:

200 m (660 ft)

Maximum temperature:

80

°C (176°F)

4-1

Advertising