<A1. Header>

6

IM 01C25R51-10E

Appendix A Flow Parameters Download Procedure

The basic procedure for downloading the flow parameters to a device is as follows. Refer to Figure A-1, A-2.

Step1

Upload from Device

Perform “Upload from Device” in the Offline Parameter screen so that the setting parameters (“Device Flow Parameters” and

“Device General Parameters”) in the device are saved to the offline database on your PC.
The parameters will then be displayed in the Offline Parameter screen.

Step2

Flow Configuration

Perform Flow configuration in accordance with the guidance in the Flow Configuration Wizard. “Device Flow Parameters” are

output by Flow Configuration Wizard.
Save “Device Flow Parameters” as XMV file (EJXMVTool) or VMV file (DYFMVTool) in the last menu, and click the “Apply”

button.
“Device Flow Parameters” are then stored to the offline database on your PC.

NOTE

Clicking on Apply does not download the flow parameters to the device.

Step3

Download to Device

Perform “Download to Device” in the Offline Parameter screen. “Device Flow Parameters” will then be downloaded together

with the “Device General Parameters” to the device.

IMPORTANT

For F

OUNDATION

Fieldbus, following block must be checked on the “Download blocks” menu in the Offline Parameter screen

to download “Device Flow Parameters” set by Flow Configuration Wizard.

EJX910 FF DTM: FTB block, DYF(SoftDL) FF DTM: AR block

“Download blocks” menu (EJX910 FF DTM)

“Download blocks” menu (DYF(SoftDL) FF DTM)

Figure A-1 “Download blocks” menu in the Offline Parameter