Installation and wiring, Installation location, Installation procedure – Yokogawa Touch Screen GP20 User Manual

Page 18

Advertising
background image

16

IM 04L51B01-02EN

Installation and Wiring

Installation Location

Install the GX/GP indoors in an environment that

meets the following conditions:

• Instrumentation panel

The GX10/GX20 excluding the portable type (GP10/

GP20) is designed to be installed in an instrumentation

panel.

• Well-ventilated location

To prevent overheating, install the GX/GP in a well-

ventilated location. For the panel cut dimensions when

arranging multiple GXs, see the next page. When

other instruments are installed next to the GX, follow

the panel cut dimensions to provide adequate space

around the GX. In the case of the portable type, we

recommend that you provide at least 50 mm of space

from the left, right, and top panels.

• Minimal mechanical vibrations

Install the GX/GP in a location that has minimal

mechanical vibrations. Installing the GX/GP

in a location that is subject to large levels of

mechanical vibration will not only put added stress

on its components, it may also impede ordinary

measurement.

• Level Location

Install the GX/GP in a level location so that it is not

slanted to the left or the right (however, the GX/GP

can be inclined up to 30 degrees backward for panel

mounting).

Note

Condensation may form when moving the GX/GP from

a low temperature or humidity environment to a high

temperature or humidity environment, or when there is a

sudden change in temperature. Temperature or humidity

changes may also result in thermocouple measurement

errors. In these kinds of circumstances, wait for at least

an hour before using the GX/GP, to acclimate it to the

surrounding environment.

The GP20 may tip over if it is tilted more than 10

degrees, front and back.

Do Not Install the Instrument in the Following Places

• Outdoors

• In direct sunlight or near heat sources

Install the GX/GP in a place that is near room

temperature (23°C) and that is not subject to large

temperature fluctuations. Placing the GX/GP in direct

sunlight or near heat sources can cause adverse

effects on the internal circuitry.

• Where an excessive amount of soot, steam, moisture,

dust, or corrosive gases are present

Soot, steam, moisture, dust, and corrosive gases will

adversely affect the GX/GP. Avoid installing the GX/GP

in such locations.

• Near strong magnetic field sources

Do not bring magnets or instruments that produce

electromagnetic fields close to the GX/GP. Operating

the GX/GP near strong magnetic fields can cause

measurement errors.

• Where the display Is difficult to see

The GX/GP uses an LCD screen, so it is difficult to

view the display from an extreme angle. Install the GX/

GP so that the user can view the display directly from

the front.

Installation Procedure

Installation Procedure for the GX10/GX20

Use a steel panel that is 2 mm to 26 mm thick.

1

Insert the GX through the front of the panel.

2

Mount the GX to the panel using the included
mounting brackets as described below.

• Use two mounting brackets to support the top and

bottom or the left and right sides of the case (remove

the stickers that are covering the holes before you

attach the brackets).

• The recommended tightening torque for the mounting

screws is 0.7 to 0.9 N•m.

• Follow the procedure below to mount the GX to the

panel.

• First, attach the two mounting brackets and

temporarily tighten the mounting screws.

• Next, fix the GX in place by tightening the mounting

screws with the appropriate torque. When the GX is

approximately perpendicular to the panel, press the

mounting brackets so that they are in contact with

the case, and fully tighten the mounting screws.

• Using more than the appropriate

torque to tighten the screws can de-

form the case or damage the brackets.

• Be sure not to insert foreign objects

or tools into the case through the

mounting bracket holes.

• When you attach the rubber pack-

ing, be sure that no portion of it gets

wedged between the GX and the

panel. If the rubber packing is not

attached properly, you will not be able

to achieve sufficient dust proofing or

waterproofing.

Note

To achieve sufficient dust proofing and waterproofing,

mount the GX in the middle of the panel cut out.