Connection to the PROFIBUS-DP Network

Cable Connection

Connect the PROFIBUS-DP cable to a PROFIBUS-DP connector provided on the back
of the DX.

5 4 3 2 1

9 8 7 6

(Rear panel)

Connector

D-sub 9-pin (female) connector. Each pin corresponds to the following signals.

Pin

Signal name

Explanation

3

RxD/TxD - P

Positive data receive/transmit.

4

CNTR - P

RTS (for use by repeater).

5

DGND

Ground.

6

VP + 5 V

+ 5 V.

8

RxD/TxD - N

Negative data receive/transmit.

Pins , 2, 7, and 9 are not used.

Cable

A dedicated two-wire cable is used (two wires for the signal). This is not supplied with the
DX. To be prepared separately.

Transmission Rate/Transmission Distance

The transmission rate varies depending on the transmission distance within the following
range.
9.6 Kbps/1200 m to 12 Mbps/100 m

Terminator

The DX has no built-in terminator circuit. If a terminator is needed in terms of wiring, use
a connector with a terminator.