Yokogawa Value Series FX1000 User Manual
Page 23

22
IM 04L21B01-02EN
Setting the Flow Rate Measurement Channel, the Input Range, the Alarm, and Tag
FX
Flowmeter
Channel 2
4 - 20 mA
Convert to 1-5 V with a shunt resistor
Setup Item
Description
Number in the Figure
Channel
Use channel 2.
1
Tag
FI-002
2
Input signal
1-5V
3
Input range
0.0 to 500.0 L/H
4
Alarm condition
Output an alarm if the measured value is
less than or equal to 120.0 L/H.
Output destination: Relay contact (I03)
5
(1) Input Range and Alarm
Press
MENU (switch to the setting mode).
Select the
Menu tab > Meas channel > Range, Alarm.
1
5
4
3
(2) Tag
Select the
Menu tab > Meas channel > Tag, Memory, Delay.
2
Operation complete.
For more details of the setting alarm, see Section 3.7 “Setting Alarms on Channels”, in
the FX1000 User’s Manual, IM 04L21B01-01EN.
Setting the Functions and Operations