Client/server settings for read, Server-side settings, Client-side settings – Yokogawa Standalone MW100 User Manual

Page 3: Server settings, Client setteing 1

Advertising
background image



IM MW100-72E

2. Computed data from MATH channels A001 to A004 of the MW100 client are written to

communication input channels C001 to C004 of the MW100 server.

For WRITE (client writes data to the server)

Lower byte of communication input channel C001

MATH Channel

Hold Register

Upper byte of communication input channel C001

Lower byte of communication input channel C002

Upper byte of communication input channel C002

Lower byte of communication input channel C004

Upper byte of communication input channel C004

40001

40002

40003

40004

40007

40008

A001

MW100 Server

MW100 Client

A002

A004

Hold register numbers assigned to the communication input

channels starting from 40001 are specified on the MW100.

“Float-Little” is selected for the register data type because

the MATH channel data is received in the order lower byte, upper byte.

Client/Server Settings for READ

Server-Side Settings

Server Settings

Set the MW100 server as the server device.

Turn on Action on the server

Turn the MODBUS server action “ON.”

Application timeout setting

Set as needed.

Timeout time for the Modbus server is fixed to 30 s.

Enter the server port number

Enter the Modbus server port number. Use the default value

unless otherwise necessary. In the example, the default value

is “502.”

Client-Side Settings

Client Setteing 1

Set the MW100 client as the client device.

Select

The setting is applied on the client device.

Set according to network environment

● Cycle:

Select a cycle appropriate for the unit’s performance.

● Connection:

Disconnect when no response is received from the server.

● Connection Timeout:

Enter the time to wait before disconnecting.

● Wait Time:

Enter the time to wait between disconnection and sending

of commands.