Page 2-21 “caution, Page 2-26 “warning, Page 3-8 “trouble shooting – Yokogawa DA100 User Manual

Page 4: Page 3-10 “about calibration, Page 4-3 standard computation functions

Advertising
background image

IM DA100-01E-88 4/6

for IM DA100-01E 8th Edition

Page 2-21 “CAUTION”

············································································································
• The power monitor module is a product belonging to Installation (Over-voltage) Category CAT II (IEC61010-1,

CSA22.2 No.61010-1).

• The power monitor module is a product belonging to Measurement Category CAT II (IEC61010-1, CSA22.2

No.61010-1).

Page 2-26 “WARNING”

············································································································
• To prevent electric shock, do not touch the terminals after wiring.
• Furnish a switch (double-pole type) to separate the instrument from the main power supply in the power

supply line. In addition, make sure to indicate that the switch is a power control for the instrument on the
switch and the ON/OFF positions of the switch.
Switch Specifications
Steady-state current rating: 3 A or more, inrush current rating: 90 A or more
Use a switch complied with IEC60947-1, -3.

• Do not add a switch or fuse to the ground line.

Page 3-8 “Trouble Shooting”

Description

Cause

Action

Reference

Page

The status indicator is
flashing in an interval
other than 1-second.

An internal error occurred. Cut the power, wait for the instrument

to cool, then, turn the power back ON
again.

2-25

Page 3-10 “About Calibration”

For “Strain measurement” under “Connection,” the wiring diagram for the bridge box used
for the DU500-14 has been changed to the following:

Connect CH2 only

Switch the

bridge head

R2

R4

R1

R3

ON

1 2 3 4 5

1

2

3

4

5

6

7

8

OFF
SW

Bridge head

(701955 or 701956)

SW1

OFF

SW2

OFF

SW3

OFF

SW4

ON

SW5

OFF

Page 4-3 Standard Computation Functions

Measurement accuracy for scaling : Measurement accuracy for scaling (digits) = Measurement

accuracy (digits) x Scaling span (digits) / Measurement

span (digits) + 2 digits (numbers below the decimal point

are rounded up).