Disposal, Specifications, 1 general – Yokogawa CTW Current Transformers User Manual

Page 2: 2 characteristic specifications, External dimensions, 1 ctw15, 2 ctw35

Advertising
background image

NOTE

When extending secondary-stage cable of the current transformer,
use a covered ring-sleeve or the like and a cable of 1.25 to 2 mm².
The standard cable length is as follows.
Up to 8.3 m for 1.25 mm², and up to 15 m for 2 mm²

4. Disposal

These current transformers, when no longer serviceable, must be disposed
of as industrial refuse.

5. Specifications

5.1 General

The CTW series are clamp-on current transformers that can be installed
much easier than conventional current transformers, whereby saving labor.
These transformers are particularly useful when expanding existing system
since you can attach them to a cable without having to cut it.

5.2 Characteristic Specifications

Rated primary current (In) / Rated secondary current:

CTW15=

100A / 1A

CTW35=

300A / 1A

Rated frequency: 50 / 60 Hz

Rated burden:

0.5 VA

Accuracy / Linearity: ±1.0% against rated primary current In

Phase difference: Within ±2° against rated primary current In

Operating circuit voltage: Within 500 V AC

Insulation resistance: 100 MΩ or more at 500 V DC (across core and

output)

Withstand voltage: 2000 V AC for one minute (across core and output)

Operating temperature range: -20 to 50°C (no condensation)

Operating conditions: Indoor location

Weight:

CTW15=

Approx. 160 g

CTW35=

Approx. 220 g

6. External Dimensions

Unit: mm

6.1 CTW15

45

1.5

(2.5)

36

39

64

AWG18

34

4

4

22

K

L

φ

24

k (White)

l (Black)

19

0

+2

0

- 0

10

+ 0

- 5

6.2

CTW35

57

1.5

45

49

80

k (White)

AWG18

38

4

4

22

K

L

φ

36

l (Black)

(2.5)

190

+20

- 0

10

+ 0

- 5

IM 77C01W03-01E 3rd Edition: 2005.01.15-00