2 condition of installation, 3 installation – Yokogawa JUXTA VJCE-01A User Manual

Page 5

Advertising
background image

5

All Rights Reserved. Copyright © 1999, Yokogawa M&C Corporation

IM 77J01C51-11E

1st Edition July 23,2004-00

3.2

Condition of Installation

NOTE

(1) Secure space for top and bottom to avoid

heating.

Apart more than 100 mm from the floor
board.

Apart more than 100 mm from panel top
and make air exhaust hole or set cooling
fan at panel upper.

If wall stands at back in case of rack
mounting, apart more than 60mm from the
wall for ventilation.

(2) Take enough space for front and side faces

so as not to interfere wiring, piping and
maintenance area.

(3) In case storing in cabinet, air cooling is

compulsorily required to prevent from raise of
temperature.

(4) Do not install it on the heating materials.
(5) In case of installing the VJCE-01A one above

another to up and down direction, take
installation space as shown in the figure on
the right. (78 mm for rack mounting, 128 mm
for wall mounting)

3.3

Installation

3.3.1

Installation of VJCE-01A

Use four (4) M5 screws for installation.

3.3.2

Installation of signal conditioners

Connect the pin on the back of the signal conditioner to the
VJCE-01A connector as shown in the figure on the right. Then
tighten the fixing screw on the front of the signal conditioner.

NOTE

Insert and pull out the signal conditioner vertically
to VJCE. Inserting and pulling it out slantwise may
make the pin bent and cause a failure such as a
bad contact.

IMPORTANT

Only one VJET can be mounted in slot 16 of VJCE-
01A. Do not mount it in other slots.

VJET

Cooling fan or exhaust hole

Cooling fan or

exhaust hole

19 inches Rack Mounting

Wall Mounting

Unit : mm

100 or more

78 or more

60 or more

100 or more

128 or more

Signal Conditioner

Fixing screw

VJCE

Blank Plate (Option)
Parts Number : T9093TT

Advertising