6.9

VJXS-J Linearizer (Optionally-set Line-segment
Function)

This computing unit gives an optional relationship between the input
(X) and output (output-1 = Y1, ouput-2 = Y2) signals using an option-
ally-set line-segment function. The line-segment function has 21
breakpoints, which each gives an input-output relationship as a per-
centage (%).
Set the number of line segments by 1 to 20.
Set the input (X) at % value in H01:CONST to H21:CONST, and the
output (Y) at % value in H22:CONST to H42:CONST.

Setting condition of breakpoints:
For input:

6.0

Ϲ

X

0

(H01) to X

20

(H21)

Ϲ

106.0%; with 4 significant

digits, minimum unit is 0.01%
X

0

<X

1

<X

2

< ····· <X

20

For output:

6.0

Ϲ

Y

0

(H22) to Y

20

(H42)

Ϲ

106.0%; with 4 significant

digits, minimum unit is 0.01%
When input

Ϲ

X

0

(H01), Y

0

(H22) is output.

When input

м

final set value, the final set value of output is output.

Any number of line segments (1 to 20) can be set in H43.
The number of line segments 1 to 20 corresponds 100 to 2000%.

Computation accuracy:

±

0.1% (However, when line-segment gain is 1 or less.)

6.10 VJXS-K Ratio Setter

This computing unit sets the ratio by the following expression.
Y1 = Y2 = K1 · (X+A1)+A2
where Y1:

Output-1 signal (%)

Y2:

Output-2 signal (%)

X:

Input signal (%)

K1:

Ratio (no unit)

A1, A2: Bias (%)

Set the ratio (K1) in H01:CONST, and the bias (A1) at % value in
H02:CONST, and the bias (A2) at % value in H03:CONST.

Setting range of ratio:

320 to 320 with 4 significant digits; minimum unit is 0.00001.

Setting range of bias:

32000 to 32000% with 4 significant digits; minimum unit is

0.001%.

Computation accuracy:

±

0.1% (However, when the ratio is 1 or less.)

NOTE

Decide ratio or bias so as not to exceed

±

3.4

ϫ

10

38

% during

computation. Ratio, bias and computation results are 4
significant digits.

Advertising