10. DESCRIPTION OF ALARM ACTIONS

This chapter describes examples of alarm actions under the following conditions.

Item

Alarm 1

Alarm 2

Parameter

Setpoint

Parameter

Setpoint

Direction of alarm action

E05 : ALM1 ACTION

High-limit alarm

E06 : ALM2 ACTION

Low-limit alarm

Alarm setting

E03 : SET POINT1

80%

E04 : SET POINT2

15%

Hysteresis

E09 : HYSTERESIS1

10%

E10 : HYSTERESIS2

5%

Alarm ON delay

E11 : ON DELAY1

1 sec

E12 : ON DELAY2

3 sec

Alarm OFF delay

E13 : OFF DELAY1

2 sec

E14 : OFF DELAY2

4 sec

Description of

alarm actions

The alarm is output if the condition where
the input value is 80% or more of high-
limit alarm continues for 1 second or
more.
After the alarm is output, when the
condition where the input value is less
than 70% of high-limit alarm continues for
2 seconds or more, the status returns to
normal.

The alarm is output if the condition where
the input value is 15% or less of low-limit
alarm continues for 3 seconds or more.
After the alarm is output, when the
condition where the input value is more
than 20% of low-limit alarm continues for
4 seconds or more, the status returns to
normal.

[%]

0

20

15

40

60

80

100

[1]

[2]

[3]

[4]

1 sec

2 sec

3 sec

4 sec

Alarm-2 hysteresis (5%)

Alarm-1 hysteresis (10%)

Alarm-1 setpoint (80%)

Alarm-2 setpoint (15%)

Elapsed time

1 sec

Alarm-1 ON delay

Alarm-1 OFF delay

Alarm conditions

established

Alarm conditions

established

Normal conditions

established

Normal conditions

established

Low-limit alarm ON

Low-limit alarm OFF

Alarm-2 ON delay

Alarm-2 OFF delay

[1]: Alarm status does not continue for more than 1 second after the

alarm conditions are established at alarm 1.

[2]: Normal status does not continue for more than 2 seconds after the

normal conditions are established at alarm 1.

[3]: Alarm status does not continue for more than 3 seconds after the

alarm conditions are established at alarm 2.

[4]: Normal status does not continue for more than 4 seconds after the

normal conditions are established at alarm 2.

Alarm conditions established

Alarm conditions established

High-limit alarm ON

High-limit alarm OFF

Normal conditions established

Normal conditions established

Alarm-1 action

Alarm-2 action

Alarm

Normal

Normal

Normal

Alarm

Normal