5. SETTING PARAMETERS

Set the parameters using a PC (VJ77 Parameter Setting Tool) or the
Handy Terminal. Refer to “6. List of Parameters” in this manual and the
User’s Manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM
JF81-02E). Parameters are indicated inside the [ ].

5.1

Setting Square Root Extractor

Set "with square root extractor" or "without square root extractor" in
[D14: LINEARIZE]. "SQR" for "with square root extractor" and "OFF"
for "without square root extractor"

5.2

Setting Lowcut Point

Set a numeric value in [D15:LOW CUT] when "with square root extrac-
tor" is selected.

Setting range: 0.3 to 100% of the input range (setting resolution:
0.1%)

Input signal (X)

Output signal

(Y)

0

Lowcut point

Hysteresis

(approx. 0.2% fixed)

Y=X

5.3

Setting Breakpoint Linearization

(1) Set the breakpoint linearization in [D14: LINEARIZE].

Select “ON” to use the breakpoint linearization.
Select “OFF” not to use the breakpoint linearization.

(2) Set the breakpoints data.

Set the input breakpoints data in [M01: X TABLE] to [M32: X
TABLE].
Set the number of breakpoints data in [M33: MAX POINT].
Set the output breakpoints data in [N01: Y TABLE] to [N32: Y
TABLE].

Setting condition of breakpoints data
Maximum number of breakpoints: 32
Setting range:

6 to 106% (both input and output)

• Set a relationship between the input and outpout at % value to

the span.

• With 4 significant digits; can be set to the second place of a

decimal point.

• For input:

6.00

Ϲ

X

0

Ͻ

X

1

Ͻ

X

2

…X

n-1

Ͻ

X

n

Ϲ

106.0%

• For output:

6.00

Ϲ

Y

0

Ͻ

Y

1

to Y

n

Ͻ

106.0%

5.4

Setting Input Range

Set the input range 0% in [D27:INPUT1 L_RNG], and the input range
100% in [D28:INPUT1 H_RNG].

5.5

Setting Output Range

Set the output range 0% in [D38:OUT1 L_RNG], and the output range
100% in [D39:OUT1 H_RNG].

NOTE

Changing the input range or output range resets the
adjusted value.

6.

LIST OF PARAMETERS

A

A01

A07

A54

A56

A58

A60

B

B01

B07

B60

D

D01

D02

D03

D04

D14

D15

D20

D22

D27

D28

D38

D39

D49

D60

M

M01

M02

:

M31

M32

M33

M60

N

N01

N02

:

N31

N32

N60

P

P08

P09

P26

P27

P60

Q

Q03

Q60

MODEL

TAG NO

SELF CHK

DISPLAY1

INPUT1

OUTPUT1

STATUS

REV NO

MENU REV

SELF CHK

DISPLAY2

INPUT1

OUTPUT1

SELF CHK

SET (I/O)

TAG NO.1

TAG NO.2

COMMENT1

COMMENT2

LINEARIZE

LOW CUT

INP TYPE

IN RESIST

INPUT1 L_RNG

INPUT1 H_RNG

OUT1 L_RNG

OUT1 H_RNG

OUT1 DR

SELF CHK

X TABLE

X TABLE

X TABLE

:

X TABLE

X TABLE

MAX POINT

SELF CHK

Y TABLE

Y TABLE

Y TABLE

:

Y TABLE

Y TABLE

SELF CHK

ADJUST

IN1 ZERO ADJ

IN1 SPAN ADJ

OUT1ZERO ADJ

OUT1SPAN ADJ

SELF CHK

TEST

OUT1 TEST

SELF CHK

Parameter Display

Item

Model

Tag number

Self-check result

Display1

Input-1

Output-1

Status *

1

REV No.

MENU REV

Self-check result

Display2

Input-1

Output-1

Self-check result

Setting (I/O)

Tag number-1

Tag number-2

Comment-1

Comment-2

Linearization

Lowcut point

*2

Input type

*3

Input resistance

*3

Input-1 low range

Input-1 high range

Output-1 low range

Output-1 high range

Direction of output-1 action

Self-check result

Input breakpoint table

Input breakpoints data

Input breakpoints data

:

Input breakpoints data

Input breakpoints data

Number of breakpoints

Self-check result

Output breakpoint table

Output breakpoints data

Output breakpoints data

:

Output breakpoints data

Output breakpoints data

Self-check result

Adjustment

Input-1 zero adjustment

Input-1 span adjustment

Output-1 zero adjustment

Output-1 span adjustment

Self-check result

Test

Forced output-1

Self-check result

*1 The displayed status is to let the service staff know the past records of the

product.

*2 The parameter becomes effective when "SQR" is selected in [D14:LINEARIZE].
*3 The parameters are the items to be set at the factory.

Advertising