Setting parameters, 6list of parameters, 1 setting burnout action – Yokogawa JUXTA MS5 User Manual

Page 4: 2 setting input range, 3 setting output range

Advertising
background image

4

IM 77J04S05-01E

1st Edition

Jul 29, 2005-00

5. SETTING PARAMETERS

Set the parameters using a PC (VJ77 Parameter Setting Tool) or the
Handy Terminal. Refer to “6. List of Parameters” in this manual and the
User’s Manual for VJ77 PC-based Parameters Setting Tool (IM
77J01J77-01E) or the User’s Manual for JHT200 Handy Terminal (IM
JF81-02E). Parameters are indicated inside the [ ].

5.1

Setting Burnout Action

Set the burnout action in [D43:BURN OUT].
Set “OFF”, “UP”, or “DOWN”.

NOTE

●

Set the burnout action before setting the input range.
Changing the burnout action setting resets the input
range.

●

Turn the adjustment switch counterclockwise to reset
the set value before setting the input range.

5.2

Setting Input Range

Set the input low range in [P16:IN1 LOW RNG], and input high range in
[P17:IN1 HIGH RNG].

(1) Resetting the input range

Select and set “RESET” in [P16:IN1 LOW RNG] or [P17:IN1 HIGH
RNG]. Then the input low range or input high range are reset.

(2) Setting the input low range

Apply the stable signal equivalent to 0% input from the connected
potentiometer. Select and set “EXECUTE” in [P16:IN1 LOW
RNG]. Then the input low range is set automatically.

(3) Setting the input high range

Apply the stable signal equivalent to 100% input from the con-
nected potentiometer. Select and set “EXECUTE” in [P17:IN1
HIGH RNG]. Then the input high range is set automatically.

5.3

Setting Output Range

Set the output range 0% in [D38:OUT1L_RNG], and the output range
100% in [D39:OUT1H_RNG].

NOTE

Changing the output range resets the adjusted value.

6

LIST OF PARAMETERS

A

A07

A54

A56

A58

A60

B

B07

B60

D

D01

D02

D03

D04

D38

D39

D43

D49

D60

P

P16

P17

P26

P27

P60

Q

Q03

Q60

MODEL

TAG NO

SELF CHK

DISPLAY1

OUTPUT1

STATUS

REV NO

MENU REV

SELF CHK

DISPLAY2

OUTPUT1

SELF CHK

SET (I/O)

TAG NO.1

TAG NO.2

COMMENT1

COMMENT2

OUT1 L_RNG

OUT1 H_RNG

BURN OUT

OUT1 DR

SELF CHK

ADJUST

IN1 LOW RNG

IN1 HIGH RNG

OUT1ZERO ADJ

OUT1SPAN ADJ

SELF CHK

TEST

OUT1 TEST

SELF CHK

Model

Tag number

Self-check result

Display1

Output-1

Status *

1

REV No.

MENU REV

Self-check result

Display2

Output-1

Self-check result

Setting (I/O)

Tag number-1

Tag number-2

Comment-1

Comment-2

Output-1 low range

Output-1 high range

Burnout

Direction of output-1 action

Self-check result

Adjustment

Setting of input-1 low range

Setting of input-1 high range

Output-1 zero adjustment

Output-1 span adjustment

Self-check result

Test

Forced output-1

Self-check result

Parameter Display

Item

*1 The displayed status is to let the service staff know the past records of the

product.