Sterling SC User Manual

Page 4

Advertising
background image

4

Table 1 - Performance and Dimensional Data - Separated Combustion Tubular Blower Unit Heater

Unit Capacity (MBH)

100

125

150

175

200

250

300

350

400

PERFORMANCE DATA†

Input - BTU/Hr.

100,000

125,000

150,000

175,000

200,000

250,000

300,000

350,000

400,000

(kW)

(29.3)

(36.6)

(44.0)

(51.3)

(58.6)

(73.3)

(87.9)

(102.6)

(117.2)

Output - BTU/Hr.

83,000

103,750

124,500

145,250

166,000

207,500

246,000

290,500

332,000

(kW)

(24.3)

(30.4)

(36.5)

(42.6)

(48.6)

(60.8)

(72.1)

(85.1)

(97.3)

Thermal Effi ciency - %

83

83

83

83

83

83

82

83

83

Free

Air

Delivery

-

CFM

1,181 1,476 1,771 2,067 2,362 2,953 3,501 4,134 4,724

(cu. m/s)

(0.557)

(0.697)

(0.836)

(0.976)

(1.115)

(1.394)

(1.652)

(1.951)

(2.230)

Air Temperature Rise - Deg. F

65

(Deg. C)

(36)

Outlet Velocity - FPM

370

463

555

395.0

451.0

564.0

422

498

570

(m/s)

(1.879)

(2.351)

(2.819)

(2.006)

(2.291)

(2.864)

(2.143)

(2.529)

(2.895)

Full Load Amps at 115V

7.3

9.4

9.4

14.2

14.2

15.6

15.6

20.8

20.8

Maximum Circuit Ampacity

8.6

11.2

11.2

17.1

17.1

18.9

18.9

25.4

25.4

MOTOR DATA:

Motor HP

1/4

1/2

3/4

1

1-1/2

Motor kW

0.19

0.37

0.56

0.75

1.11

Motor Type**

SPH

SPH

SPH

Cap. Start

Cap. Start

RPM

1,725

1,725 1,725 1,725 1,725

Amps @ 115V

5.1

7.2

11.6

13.0

18.2

DIMENSIONAL DATA - inches (mm)

"A" Height to Top of Flue

33-3/4

34

(857)

(864)

"B" Jacket Width of Unit

20-3/4

32-3/4

50-3/4

(527)

(832)

(1289)

"C" Width to Centerline Flue

13-3/8

19-3/8

28-3/8

(340)

(492)

(721)

"D" Depth to Front Hanger

21

(533)

"E" Hanging Distance Width

18-5/8

30-5/8

48-5/8

(473)

(778)

(1235)

"F" Hanging Distance Depth

19

19-1/2

32-3/4

23-1/2

32-3/4

(483)

(495)

(832)

(597)

(832)

"G" Discharge Opening Width

18-3/4

30-3/4

48-3/4

(476)

(781)

(1238)

"H" Depth to Centerline Flue

4-3/4

5-1/8

(121)

(130)

"M" Overall Unit Width

25-1/4

37-1/4

55-1/4

(641)

(946)

(1403)

"P" Overall Unit Depth

49-3/4

49-3/8

56-1/8

53-3/8

56-1/8

(1264)

(1254)

(1426)

(1356)

(1426)

*Flue Size Diameter - in

5

6

(mm)

(127)

(152)

Gas Inlet, Natural Gas - in

1/2

3/4

Gas Inlet, LP Gas - in

1/2

1/2 OR 3/4

Approximate Unit Weight - lb

173

177

204

248

267

292

374

394

433

(kg)

(78)

(80)

(92)

(112)

(121)

(132)

(170)

(179)

(196)

Approximate Ship Weight - lb

258

263

291

384

403

428

524

551

599

(kg)

(117)

(119)

(132)

(174)

(183)

(194)

(238)

(250)

(272)

† Ratings shown are for unit installations at elevations between 0 and 2,000 ft (0 to 610m). For unit installations in U.S.A. above 2,000 ft. (610m), the unit input must be fi eld derated 4% for each

1,000 ft. (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas Code, ANSI Standard Z223.1 (N.F.P.A. No. 54).

For installations in Canada, any reference to deration at altitudes in excess of 2,000 ft. (610m) are to be ignored. At altitudes of 2,000 ft. to 4,500 ft. (610 to 1372m), the unit must be fi eld derated

to 90% of the normal altitude rating, and be so marked in accordance with the ETL certifi cation. See Table 8A for fi eld deration information.

* Flue collar is factory supplied with unit; to be fi eld installed per included instructions.

** LEGEND:

SPH = SPLIT PHASE CAP. START = CAPACITOR START