Table 1 - Performance and Dimensional Data - Tubular 30 thru 120 Propeller Unit Heater
Unit
Size
30 45 60 75 90 105
120
PERFORMANCE DATA†
Input
-
BTU/Hr.
30,000 45,000 60,000 75,000 90,000 105,000
120,000
(kW)
(8.8)
(13.2)
(17.6)
(22.0)
(26.4)
(30.8)
(35.2)
Output
-
BTU/Hr.
24,900 37,350 49,800 61,500 73,800 86,100 98,400
(kW)
(7.2)
(10.9)
(14.5)
(18.0)
(21.6)
(25.2)
(28.8)
Thermal
Effi
ciency
(%)
83 83 83 82 82 82 82
Free Air Delivery - CFM
370
550
740
920
1,100
1,300
1,475
(cu. m/s)
(.175)
(.260)
(.349)
(.434)
(.519)
(.614)
(.696)
Air
Temperature
Rise
-
°F
60 60 60 60 60 60 60
(°C)
(15)
(15)
(15)
(15)
(15)
(15)
(15)
Full
Load
Amps
at
120V
3.0 3.0 4.1 4.1 6.4 6.4 6.4
Maximum
Circuit
Ampacity
3.5 3.5 4.8 4.8 7.5 7.5 7.5
MOTOR DATA: Motor HP
1/20
1/20 1/12 1/12 1/10 1/10 1/10
Motor
(kW)
(0.04) (0.04) (0.06) (0.06) (0.075)
(0.075)
(0.075)
Motor
Type
SP SP SP SP SP SP SP
RPM
1650 1650 1050 1050 1050 1050 1050
Motor
Amps
@
115V
1.9 1.9 2.6 2.6 4.2 4.2 4.2
DIMENSIONAL DATA - inches (mm)
“A”
Jacket
Height
12-3/8 12-3/8 15-7/8 15-7/8 22-5/8 22-5/8 22-5/8
(314) (314) (403) (403) (574) (574) (574)
“B” Overall Height
13-1/4
13-1/4
16-13/16
16-13/16
23-9/16
23-9/16
23-9/16
(337) (337) (427) (427) (598) (598) (598)
“C”
Overall
Depth
25-7/8 25-7/8 26-3/16
26-3/16 26-3/8 26-3/8 26-3/8
(632) (632) (665) (665) (670) (670) (670)
“D1” Center Line Height of Flue*
8-1/2
8-1/2
10-3/8
10-3/8
13-5/8
13-5/8
13-5/8
(216) (216) (263) (263) (346) (346) (346)
“D2” Center Line Height of Air Intake
8-1/2
8-1/2
8
8
8-5/8
8-5/8
8-5/8
(216) (216) (203) (203) (219) (219) (219)
“E”
Fan
Diameter
10 10 14 14 16 16 16
(254) (254) (356) (356) (406) (406) (406)
“F” Discharge Opening Height
10-13/16
10-13/16
14-7/16
14-7/16
21-3/16
21-3/16
21-3/16
(275) (275) (367) (367) (538) (538) (538)
“G”
Flue
Vent
Connection
Diameter
(Min.) 4 4 4 4 4 4 4
(102) (102) (102) (102) (102) (102) (102)
“H1” Center Line of Flue Connection From Side
7-1/4
7-1/4
7-1/4
7-1/4
7-3/4
7-3/4
7-3/4
(184) (184) (184) (184) (197) (197) (197)
“H2” Center Line of Air Intake From Side
2-3/4
2-3/4
2-3/4
2-3/4
3-1/2
3-1/2
3-1/2
(70) (70) (70) (70) (89) (89) (89)
Vent Size Requirements - Standard Combustion
Category III Horizontal
4
4
4
4
4
4
4
(102) (102) (102) (102) (102) (102) (102)
Category I & III Vertical
4
4
4
4
4
4
4
(102) (102) (102) (102) (102) (102) (102)
Vent Size Requirements - Separated Combustion
Exhaust Diameter
4
4
4
4
5
5
5
(102) (102) (102) (102) (127) (127) (127)
Intake Air Diameter
4
4
4
4
5
5
5
(102) (102) (102) (102) (127) (127) (127)
Unit
Weight
-
lbs.
60 65 80 85 95 105
110
(kgs)
(27)
(29)
(36)
(39)
(43)
(48)
(50)
Shipping
Weight
-
lbs.
70 75 90 95 110
115
120
(kgs)
(32) (34) (41) (43) (50) (52) (54)
* For all installations, the fl ue collar is included with the unit and should be fi eld installed per the instructions included with the unit.
† Ratings shown are for unit installations at elevations between 0 and 2,000 feet (0 to 610m). For unit installations in U.S.A. above 2,000 feet (610m), the unit input
must be derated 4% for each 1,000 feet (305m) above sea level; refer to local codes, or in absence of local codes, refer to the latest edition of the National Fuel Gas
Code, ANSI Standard Z223.1 (NFPA No. 54), (also refer to Table 7).
For installations in Canada, any reference to deration at altitudes in excess of 2,000 feet (610m) are to be ignored. At altitudes of 2,000 feet to 4,500 feet (610 to
1372m), the unit must be derated and be so marked in accordance with the ETL certifi cation. See Table 7 for USA and Canadian fi eld deration information.