Accessing stored data – MAHLE RTI Matco AC880 User Manual

Page 13

Advertising
background image

Page 12

W E I G H T =

X X . X

L B

A U T O M A T I C

?

5

>>>>>

ENTER

W E I G H T =

X X . X

L B

S E T U P

?

5

ENTER

F I L T E R

H O U R S =

X X . X

H O U R S

>

T O T A L

R E C Y C L E D =

X X X X . X

K G

>

T O T A L

C H A R G E D =

X X X X . X

K G

>

Accessing Stored Data

1.

Setup the AC880 as shown on Page 4 and then turn the Main Power Switch
ON.

2.

Using the Keypad, press the “Up Arrow” key five times to display “WEIGHT=
XX.X LB” “SETUP? 5” and then press the ENTER key. The Display will read
“FILTER HOURS=” “XX.X HOURS”.

See the Filter Maintenance section of the manual, Page 14, for the procedure
to change the filters. The normal Filter Change Interval is after every 25
hours.

Note: Press and hold the “Right Arrow” key and press the RESET key to

remove the “CHANGE FILTERS 5” message.

3.

Press the “Up Arrow” key. The Display will read “TOTAL RECYCLED=”
“XXXX.X KG”.

4.

Press the “Up Arrow” key. The Display will read “TOTAL CHARGED=”
“XXXX.X KG”.

5.

Press the “Up Arrow” key to return to the Main Menu.