- 15.3 -


Appendixes



C:\RHS Computer Files\Instructions\RHS\GB\645-40\0009A-01.doc 1997.03.26
RHS 700

Test 3:

High pressure

Approx. 7 - 15 bar

Low pressure

Approx. 1.5 bar

Fault/problem

Symptom

Possible cause

Remedy

A/C unit runs irregu-
larly

Varying pressures on
high and low-pressure
sides

Moisture in A/C unit
causes ice on expan-
sion valve and reduces
output.

Filter drier saturated

Empty, evacuate and
recharge A/C unit.
After recovery process
replace filter drier. If
necessary, remove and
clean expansion valve.
Replace valve or fit
new valve.



Test 4:

High pressure

Approx. 6 bar

Low pressure

Approx. -0.3 bar

Fault/problem

Symptom

Possible cause

Remedy

A/C unit does not cool
- or cools only slightly

Hoses ahead of or after
expansion valve or
filter drier covered
with moisture or ice

Because of moisture in
A/C unit, expansion
valve or filter drier
blocked by ice

Cut out A/C unit, wait
a few minutes and
empty it. Then eva-
cuate and recharge
A/C unit.