CPS20 Instruction Manual for Power Supplies
CPS20 Bedienungsanleitung für Stromversorgungen


Technical Data

1)

Technische

Daten

1)

CPS20.121

CPS20.241

CPS20.241-C1

2)

CPS20.361

CPS20.481

Output Voltage

Ausgangsspannung

nom.

DC 12-15V

DC 24-28V

DC 36-42V

DC 48-56V

Factory Setting at Full Load

Werkseinstellung bei Nennlast

“Single-Use”, typ.

12.0V

24.1V

36.0V

48.0V

Output Current

continuous Ausgangsstrom

dauernd

nom.

30A at 12V
27A at 15V

20A at 24V

17.1A at 28V

13.3A at 36V
11.4A at 42V

10A at 48V

8.6A at 56V

Output Current

PowerBoost

14)

Ausgangsstrom PowerBoost

14)

nom.

-

24A at 24V

20.6A at 28V

16A at 36V

13.7A at 42V

12A at 48V

10.3A at 56V

short-term (15ms)

kurzzeitig (15ms)

120A

80A

45A

40A

Output Power

continuous Ausgangsleistung

dauernd

nom.

360/ 405W at 12/ 15V

480W

480W

480W

Output Power

PowerBoost

14)

Ausgangsleistung

PowerBoost

14)

nom.

-

576W 576W

576W

Output Ripple & Noise Voltage

13)

Ausgangswelligkeit

13)

max.

100mVpp

50mVpp 100mVpp

50mVpp

Output Overload Behavior

Überlastverhalten am Ausgang

-

Hiccup

PLUS

17)

Hiccup

PLUS 17)

Hiccup

PLUS 17)

Hiccup

PLUS 17)

AC Input Voltage

AC Eingangsspannung

nom.

AC 100-240V

-15%/+10%

AC 100-240V

15)

-15%/+10%

AC 100-240V

15)

-15%/+10%

AC 100-240V

15)

-15%/+10%

Input Frequency

Eingangsfrequenz

nom.

50-60Hz

±6%

50-60Hz

±6%

50-60Hz

±6%

50-60Hz

±6%

AC Input Current

3)

AC

Eingangsstrom

3)

typ.

3.3A / 1.8A

4.36A / 2.33A

4.36A / 2.33A

4.36A / 2.33A

Power Factor

3)

Leistungsfaktor

3)

typ.

0.99 / 0.95

0.99 / 0.95

0.99 / 0.95

0.99 / 0.95

Allowed Voltage L or N to Earth

Erlaubte Spannung L oder N zu Erde

max.

300Vac

300Vac 300Vac

300Vac

PFC Norm EN 61000-3-2 Class A

PFC Norm EN 61000-3-2 Klasse A

-

Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

DC Input Voltage

DC Eingangsspannung

nom.

-

10) -

10)

Input Inrush Current

3) 4)

Einschaltspitzenstrom

3) 4)

typ.

9A / 7A peak

9A / 7A peak

9A / 7A peak

9A / 7A peak

Hold-up Time

3)

Pufferzeit

3)

typ.

35ms / 35ms (at 12V)

26ms / 26ms

26ms / 26ms

26ms / 26ms

Efficiency

3)

Wirkungsgrad

3)

typ.

90.9% / 92.6%

92.7% / 94.0%

93.0% / 94.3%

92.6% / 93.9%

Power Losses

3)

Verlustleistung

3)

typ.

33.9W / 28.8W

37.8W / 30.6W

36.1W / 29.0W

38.4W / 31.2W

Operational Temperature Range

18)

Betriebstemperaturbereich

18)

nom.

-25°C - +70°C

-25°C - +70°C

-25°C - +70°C

-25°C - +70°C

Output Derating

Leistungsrücknahme

+60°C to +70°C

0.75A/°C

12W/°C

12W/°C

12W/°C

Storage Temperature Range

Lagertemperaturbereich

nom.

-40°C - +85°C

-40°C - +85°C

-40°C - +85°C

-40°C - +85°C

Humidity

5)

Feuchte

5)

IEC 60068-2-30

5 - 95% r.H.

5 - 95% r.H.

5 - 95% r.H.

5 - 95% r.H.

Vibration Schwingen IEC 60068-2-6

2g

16)

2g

16)

2g

16)

2g

16)

Shock Schocken

IEC 60068-2-27

30g 6ms, 20g 11ms

16)

30g 6ms, 20g 11ms

16)

30g

6ms, 20g 11ms

16)

30g 6ms, 20g 11ms

16)

Degree of Pollution

Verschmutzungsgrad

IEC 62103

2

5) 19)

2

5) 19)

2

5) 19)

2

5) 19)

Degree of Protection

Schutzart

EN 60529

IP20

IP20

IP20

IP20

Class of Protection

Schutzklasse

IEC 61140

I

6)

I

6)

I

6)

I

6)

Over-temperature Protection

Übertemperaturschutz

OTP

Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Output Over-voltage Protection Überspannungsschutz

am

Ausgang

OVP, max.

18Vdc

32Vdc

50Vdc

60Vdc

Return Voltage Resistance

8)

Rückspeisefestigkeit

8)

max.

16Vdc

35Vdc 50Vdc

63Vdc

Leakage Current

7)

TN/TT-mains

IT-mains

PE- Ableitstrom

7)

TN/TT-Netze

IT-Netze

max.
max.

0.26mA / 0.46mA
0.67mA / 1.08mA

0.26mA / 0.46mA
0.67mA / 1.08mA

0.26mA / 0.46mA
0.67mA / 1.08mA

0.26mA / 0.46mA
0.67mA / 1.08mA

Parallel Use

11)

Parallelschaltbar

11)

-

Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Serial Use

12)

Serienschaltbar

12)

-

Yes / Ja

Yes / Ja

Yes / Ja

Yes / Ja

Dimensions

9)

(WxHxD) Abmessungen

9)

(BxHxT)

nom.

65x124x127mm

65x124x127mm 65x124x127mm

65x124x127mm

Weight Gewicht

max.

1000g, 2.2lb

1000g, 2.2lb

1000g, 2.2lb

1000g, 2.2lb

1) All parameters are specified at 230Vac input voltage, nominal output current, “Single Use”

setting, 25°C ambient and after a 5 minutes run-in time unless otherwise noted.

2) -C1: Version with conformal coated PC-boards.
3) at 120Vac / 230Vac
4) Input inrush current is electronically limited, temperature independent and is valid for mains

interruptions > 500ms

5) Do not energize while condensation is present.
6) PE connection required (Ground).
7) Leakage current at 132Vac, 60Hz / 264Vac, 50Hz
8) Loads such as decelerating motors and inductors can feed voltage back to the output of the

power supply. The figure represents the maximum allowed feed back voltage

9) Depth without DIN-rail.
10) Use CPS20.241-D1 or CPS20.481-D1
11) Set jumper on the front to “Parallel Use”. A fuse (or diode) on the output is required if more

than three units are paralleled.

12) Use only power supplies of the same type. The total output voltage should not be >150Vdc.
13) 50-Ohm measurement, bandwidth 20MHz
14) The PowerBoost is continuously allowed up to an ambient temperature of 45°C. Above 45°C,

do not use the PowerBoost longer than a duty cycle of 10% and/ or not longer than max. 1
minute every 10 minutes.

15) An output current derating might be necessary at input voltages below 100Vac, see figure 7.
16) Higher levels possible when utilizing the wall mounting bracket ZM2.WALL
17) Hiccup

PLUS

is an overload behavior with a balanced power management. In normal mode it

provides generous power reserves but effectively protects connected equipment and cables
against damage in the event of failure. More details on the next pages.

18) The operational temperature range equals the surrounding air temperature measured 2cm

below the unit.

19) Caution: For use in a controlled environment according to CSA 22.2 No 107.1-01.

1) Alle Werte gelten bei 230Vac Eingangsspannung, Nennausgangsstrom, „Single-Use“ Modus,

25°C Umgebung und nach einer Aufwärmzeit von 5 Minuten, falls nichts anderes angegeben.

2) -C1: Version mit schutzlackierten Leiterplatten.
3) bei 120Vac / 230Vac
4) Der Einschaltstromstoß ist elektronisch begrenzt, temperaturunabhängig und gilt für

Netzunterbrechungen > 500ms

5) Nicht betreiben, solange das Gerät Kondensation aufweist.
6) PE Verbindung erforderlich.
7) Ableitstrom bei 132Vac, 60Hz / 264Vac, 50Hz
8) Bremsende Motoren oder Induktivitäten können Spannung zum Ausgang des Netzteils

rückspeisen. Der Wert gibt die max. zulässige Rückspeisespannung an.

9) Tiefe ohne DIN-Schiene
10) CPS20.241-D1 und CPS20.481-D1 sind für DC-Eingangsspannungen geeignet
11) Steckbrücke an der Front des Gerätes auf „Parallel Use“ umstellen. Bei mehr als drei Geräten

wird eine Sicherung oder eine Diode zur Entkopplung benötigt.

12) Nur für gleiche Geräte bis zu einer Gesamtspannung von 150Vdc
13) 50-Ohm Messung, Bandbreite 20MHz
14) Der PowerBoost ist bis zu einer Umgebungstemperatur von +45°C dauerhaft erlaubt. Darüber

soll sie nicht länger als 10% (<1 Minute alle 10 Minuten) entnommen werden.

15) Unterhalb 100Vac kann eine Leistungsrücknahme erforderlich sein. Siehe Bild 7.
16) Höhere Werte sind bei Verwendung des Wandmontageadapters ZM2.WALL möglich
17) Hiccup

PLUS

ist ein Überlastverhalten mit einem ausgewogenem Leistungsmanagement,

welches im Normalbetrieb kurzzeitig großzügige Leistungsreserven zur Verfügung stellt, aber
im Fehlerfall angeschlossene Verbraucher und Kabel effektiv vor Schäden schützt. Mehr