Mammoth V-Cube Slim E-Series (Air Handler Version) User Manual

Page 6

Advertising
background image

6

MAMM-VCS-IOM-2EB (October 2011)

Remove the water pipe extensions at the Victaulic con-
nection point inside the unit. Attach lifting straps to the
motor mount plate as shown in Figure 4 and attach to a
spreader bar or forklift fork. Also attach ropes or chains
to the eye bolt on one of the motors and attach to each
end of the spreader bar or fork to level the load of the
blower section.


Use these instructions in the reverse order for assem-
bly. Replace any torn or damaged gasket with new
material. Apply a bead of silicon caulking between sec-
tions while reassembling to minimize air leaks.

For further information or assistance with these proce-
dures, contact the Mammoth Service department.



Step 2 – Remove optional heating coil section
This step only applies to units with an optional heating
coil.

Remove the bolts that connect the welded base of the
heating coil section to the welded base of the main
cabinet section.

Remove the access panels on each side of the optional
heating coil cabinet shown in Figure 2. Inside the op-
tional heating coil section, disconnect wiring to any
valves and/or air sensors that run to the other sections
in the unit.

Once all electrical connections to the other sections in
the unit have been removed, loosen and remove the
section bolts that fasten the optional heating coil cabi-
net to the main cabinet. Set the optional heating coil
section aside, away from the unit to help prevent dam-
age during the remaining disassembly process.

Step 3 – Removing the blower cabinet
Remove the main cabinet access panels (Figure 3).

Feed any wiring for the blower motors and/or air sen-
sors passing through the coil section through the chase
way into the blower cabinet.

Remove the section bolts that attach the blower cabinet
to the coil section (Figure 3).

Figure 2—Optional Heating Coil Section Removal

Figure 3—Removal of Blower Section Bolts

Remove Section Bolts

Remove Section Bolts

Figure 4—Lifting the Blower Section

CAUTION!

Lifting straps are to be used in lifting the blower section
only. Do not attach eye bolts to the motor mount plate
and attempt to lift the blower section. Failure to do so
can result in equipment damage and personal injury.