I/o 560 (base cav) - examples of i/o’s – Mammoth 1/2 to 6 Tons: High Efficiency Single Circuit Horizontal and Vertical (A-Vintage) User Manual

Page 13

Advertising
background image

13

MAMM-WSHP-IOM-1MA

I/O 560 (Base CAV) - Examples of I/O’s

Universal

Input

Jumper Setting

1

Supply Air Temperature (Monitor Only)

Thermistor/Dry Contact

2

Condenser Leaving Water Temperature

Thermistor/Dry Contact

3

Thermistor/Dry Contact

4

Compr Lckt/Overflow

Compr.#1 HP-5 Alarm

Compr. #2 Alarm

Thermistor/Dry Contact

5

Load Shead*

Compr#1Q HP-5 Alarm*

Compr#2Q HP-5 Alarm

Thermistor/Dry Contact

6

Emergency Shut Down External Clock (Start)

Dirty Filter (Switch Opt)

Thermistor/Dry Contact

Condenser Entering Water Temperature

Rnet

Jumper Setting

1

Room/Return Air Temperature (RS Std) or
Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)

N/A

Digital

Output

Jumper Setting

1

Supply Fan Start

Dry Contact for 24 VAC

2

Compressor Call #1

Dry Contact for 24 VAC

3

Compressor Call #2 or on/off Waterside Economize or on/off Aux. Heat

Dry Contact for 24 VAC

4

Reversing Valve or on/off Waterside Economizer or on/off Aux. Heat

Dry Contact for 24 VAC

5

Common Alarm

Dry Contact for 24 VAC

Options are in italics. Common options are bolded

* Cost add option must be ordered to get multiplexing board
** A minimum of one keypad display must be ordered per project to set required set-points
*** A protocol will be a cost add option