I/O 560 (Base CAV) - Examples of I/O’s
Universal
Input
Jumper Setting
1
Supply Air Temperature (Monitor Only)
Thermistor/Dry Contact
2
Condenser Leaving Water Temperature
Thermistor/Dry Contact
3
Thermistor/Dry Contact
4
Compr Lckt/Overflow
Compr.#1 HP-5 Alarm
Compr. #2 Alarm
Thermistor/Dry Contact
5
Load Shead*
Compr#1Q HP-5 Alarm*
Compr#2Q HP-5 Alarm
Thermistor/Dry Contact
6
Emergency Shut Down External Clock (Start)
Dirty Filter (Switch Opt)
Thermistor/Dry Contact
Condenser Entering Water Temperature
Rnet
Jumper Setting
1
Room/Return Air Temperature (RS Std) or
Room Air Temperature/Stet-Point/Override (RS-Pro, Optional)
N/A
Digital
Output
Jumper Setting
1
Supply Fan Start
Dry Contact for 24 VAC
2
Compressor Call #1
Dry Contact for 24 VAC
3
Compressor Call #2 or on/off Waterside Economize or on/off Aux. Heat
Dry Contact for 24 VAC
4
Reversing Valve or on/off Waterside Economizer or on/off Aux. Heat
Dry Contact for 24 VAC
5
Common Alarm
Dry Contact for 24 VAC
Options are in italics. Common options are bolded
* Cost add option must be ordered to get multiplexing board
** A minimum of one keypad display must be ordered per project to set required set-points
*** A protocol will be a cost add option