STI SS-2000F User Manual

Page 2

Advertising
background image

IF LAST

STATION ON

CIRCUIT,

CONNECT E.O.L.

RESISTOR

12-18 AWG

CLOSE ON
ALARM

SINGLE DEVICE

DIAGRAM DEPICTING
MULTIPLE DEVICES

12-18 AWG

CLOSE ON
ALARM

SUPERVISED LOOP (SEE CAUTION NOTE)

CLOSE ON
ALARM

BE SURE ALL ELECTRICAL

POWER IS DISCONNECTED

BEFORE STARTING THE INSTALLATION.

NOTE: JUMPER NOT PROVIDED

A

VIEW IN DIRECTIONS OF ARROW

INSTALLATION AND REMOVAL OF TERMINAL BLOCKS AND

TERMINAL BLOCK ASSEMBLY FROM BUTTON ASSEMBLY

TO SEPARATE TERMINAL
AND BUTTON ASSEMBLY

GRASP TERMINAL HOUSING, USING
THUMB APPLY PRESSURE
DOWNWARD, REMOVE TERMINAL
HOUSING AS SHOWN.

REMOVAL OF TERMINAL BLOCK
FROM TERMINAL HOUSING

INSERT SMALL SCREWDRIVER
AS SHOWN AND PRY
UPWARD, REMOVE TERMINAL.

BACKPLATE ASSEMBLY

INSERT NOTCH

AS SHOWN THEN
ROTATE UPWARD

TERMINAL BLOCK RELEASE LEVER
MUST FACE UPWARD
AS SHOWN FOR SWITCH
TO FUNCTION CORRECTLY.

ELECTRICAL TERMINAL
1, 2, OR 3 TERMINALS
MAY BE USED

STRIP 1/4 in. OF WIRE INSULATION,
INSERT IN TERMINAL (AS SHOWN).
THEN USING A PHILLIPS SCREWDRIVER
TURN CLOCKWISE UNTIL TIGHT.

A

VIEW IN DIRECTIONS OF ARROW

INSTALLATION OF ELECTRICAL
WIRE INTO TERMINAL BLOCK

OUTGOING

INCOMING

BUTTON LOCK NUT

10196 N.O. TERMINAL BLOCK
(2) PROVIDED UP TO 3
TERMINALS MAY BE USED FOR
EACH STATION ASSEMBLY.

A

AN UNINSULATED SECTION OF A SINGLE
CONDUCTOR SHOULD NOT BE LOOPED
AROUND THE TERMINAL AND SERVE AS
TWO CONNECTIONS.
THE WIRE MUST BE SEVERED, THEREBY
PROVIDING SUPERVISION OF THE
CONNECTION IN THE EVENT THE WIRE
BECOMES DISLODGED FROM THE DEVICE.

CAUTION

METAL WASHER

ALL TERMINALS ACCEPT TWO 12 TO 18 (AWG)

VOLTAGE

RATED AVERAGE CURRENT

250 VDC

1 AMP

24 VAC

3 AMP

SAFETY TECHNOLOGY INTERNATIONAL, INC. • 2306 AIRPORT ROAD • WATERFORD • MICHIGAN 48327-1209 • PHONE: 248-673-9898 • FAX: 248-673-1246 • INFO @ www.sti-usa.com

SHT. 2

10277IS JAN99