Switch rating – STI SUB-UB-1C User Manual

Page 2

Advertising
background image

- 2 -

NOTES

It is important to read, understand and follow all instructions provided
with this product. It is the installer’s responsibility to comply with NFPA
70 & 101, NEC, mounting specifications according to ADA and other ap-
plicable electrical codes. For Type SM (Self Monitored) rating, the term
Emergency message may be installed on Model UB-1 when used in a sys-
tem with a Listed, compatible Releasing Device. All other applications are
rated Type NM (Non-Monitored) for non-emergency signaling. To avoid
electrical shock, DO NOT attempt to install this product when power is on.
ADA mounting compliance requires the operable part of the initiating de-
vice shall not be less than 3 1/2 ft. (1.1m ) or greater than 4 1/2 ft.
(1.37m) above finished floor surface. After installation and testing are
complete, provide a copy of this manual to all personnel responsible for
testing and maintenance of this product.

SWITCH RATING

2 Momentary Independent Form “C” contacts

UB-1/rated at: 10A, 1/2 HP, 125/250 VAC
6A, 30 VDC

100,000 Operations
Temperature: -40° to 185°F (-40° to 85°C)

Model UB-1/LTUL
Form C contacts on
Timer rated:
30 VDC 3A, 1.0 pf

BUTTON ACTIVATED

M


4.830 in.

(123mm)

3.220 in.

(82mm)

1.328 in.

(34mm)

.867 in.

(22mm)

Advertising
This manual is related to the following products: