Electrical considerations, Environmental considerations, Cabinet considerations – Brocade 5300 Hardware Reference Manual User Manual

Page 20: Recommendations for cable management

Advertising
background image

8

Brocade 5300 Hardware Reference Manual

53-1000858-04

Installation and safety considerations

2

Electrical considerations

To install and operate the switch successfully, ensure the following:

•

The primary outlet is correctly wired, protected by a circuit breaker, and grounded in
accordance with local electrical codes.

•

The supply circuit, line fusing, and wire size are adequate, as specified by the electrical
rating on the switch nameplate.

•

The power supply standards provided in

Table 6

,

“Power Supply Specifications”

on

page 28 are met.

Environmental considerations

For successful installation and operation of the switch, ensure that the following environmental
requirements are met:

•

At a minimum, adequate cooling requires that you install the switch with the non-port side,
which contains the air intake vents, facing the cool-air aisle.

•

All equipment in the rack should force air in the same direction to avoid intake of exhaust
air.

•

A maximum of 102 cubic meters/hour (60 cubic feet/minute) and a minimum of 74.8
cubic meters/hour (44 cubic feet/minute) of air flow is available to the air intake vents on
the non-port side of the switch.

•

The ambient air temperature does not exceed 40

C (104

F) while the switch is operating.

Cabinet considerations

For successful installation and operation of the switch in a cabinet, ensure the following cabinet
requirements are met:

•

The cabinet must be a standard EIA cabinet.

•

Plan a cabinet space that is one rack unit (1U) high; 4.45 cm (1.75 inches) high and 48.3
cm (19 inches) wide.

•

Ground all equipment in the cabinet through a reliable branch circuit connection and
maintain ground at all times. Do not rely on a secondary connection to a branch circuit,
such as a power strip.

•

Ensure that airflow and temperature requirements are met on an ongoing basis,
particularly if the switch is installed in a closed or multicabinet assembly.

•

Verify that the additional weight of the switch does not exceed the cabinet’s weight limits
or unbalance the cabinet in any way.

•

Secure the cabinet to ensure stability in case of unexpected movement, such as an
earthquake.

Recommendations for cable management

The minimum bend radius for a 50 micron cable is 2 inches under full tensile load and 1.2 inches
with no tensile load.