Environmental considerations, Rack considerations, Environmental considerations rack considerations – Brocade 6520 Hardware Reference Manual User Manual

Page 20

Advertising
background image

8

Brocade 6520 Hardware Reference Manual

53-1002705-02

Installation and safety considerations

2

Environmental considerations

For successful installation and operation of the switch, ensure that the following environmental
requirements are met:

•

At a minimum, adequate cooling requires that you install the switch with the intake side, as
indicated by the airflow direction of the fan assemblies, facing the cool-air aisle.
The chassisshow output indicates “Reverse” for non-port side intake and “Forward” for port
side intake.

•

All equipment in the rack should force air in the same direction to avoid intake of exhaust air.

•

Airflow requirements outlined in

Table 5

must be met. Note that the requirements differ based

on the direction of the airflow.

•

The ambient air temperature does not exceed 40

°

C (104

°

F) while the switch is operating.

Table 5

lists the acceptable environmental ranges for both operating and nonoperating (such as

during transportation or storage) conditions.

Rack considerations

For successful installation and operation of the switch in a rack, ensure the following rack
requirements are met:

•

The rack must be a standard EIA rack.

•

A rack space that is two rack units (2U) high; 8.90 cm (3.50 inches) high and 48.3 cm (19
inches) wide.

•

There are three rack kit options that accommodate the Brocade 6520, a four-post fixed rack
kit, a two-post Telco rack kit, and a four-post sliding rail rack kit. See their respective
installation manuals for details.

TABLE 5

Environmental requirements

Condition

Acceptable during operation

Acceptable during non-operation

Ambient
temperature

0º to 40ºC (32º to 104ºF)

-25º to 70ºC (-13º to 158ºF)

Humidity

10% to 85% RH non-condensing, at
40ºC (104ºF)

10% to 90% RH non-condensing, at 70ºC
(158ºF)

Altitude

0 to 3 km (9,842 feet) above sea level

0 to 12 km (39,370 feet) above sea level

Shock

20 G, 6 ms, half-sine wave

33 G, 11 ms, half-sine wave, 3/eg Axis

Vibration

0.5 G sine, 0.4 gms random, 5-500 Hz

2.0 G sine, 1.1 gms random, 5-500 Hz

Air flow

Port side exhaust -

Maximum - 176.7 cmh (104 cfm)
Nominal - 52.7 cmh (31 cfm)

Port side intake -

Maximum - 185.2 cmh (109 cfm)
Nominal - 56.1 cmh (33 cfm)

N/A

Heat dissipation

1378.5 BTU/hr (no optics configuration)
1706.1 BTU/hr (fully populated port
configuration)

N/A