Installation, Warning, Line cord connection – Lincoln Electric IM810 PRO-MIG 175 User Manual

Page 13: Electrical input connection for rated output, 230 volt input connection, 208 volt input connection

Advertising
background image

A-6

A-6

INSTALLATION

Line Cord Connection

A 3 conductor line cord with a 50 amp, 250 volt, three-
prong plug (NEMA Type 6-50P) is factory installed.
Connect this plug to a mating grounded receptacle
which is connected to an appropriate power supply
per the U.S. National Electric Code and any applica-
ble local codes.

CONNECT TO A SYSTEM
GROUNDING WIRE. SEE
THE UNITED STATES
NATIONAL ELECTRICAL
CODE AND/OR LOCAL
CODES FOR OTHER
DETAILS AND MEANS FOR
PROPER GROUNDING.

CONNECT TO HOT WIRES
OF A THREE-WIRE SINGLE
PHASE SYSTEM OR TO
ONE PHASE OF A TWO OR
THREE PHASE SYSTEM.

This welding machine must be connected to a
power source in accordance with applicable elec-
trical codes.

The Electrical Code provides standards for
amperage handling capability of supply conduc-
tors based on duty cycle of the welding source.

If there is any question about the installation
meeting applicable electrical code requirements,
consult a qualified electrician.
-----------------------------------------------------------------------

ELECTRICAL INPUT CONNECTION FOR
RATED OUTPUT

ELECTRIC SHOCK can kill.

• Disconnect input power by remov-

ing plug from receptacle before
working inside Pro-MIG 175.

• Use only grounded receptacle.

• Do not touch electrically “hot” parts inside Pro-

MIG 175.

• Have qualified personnel do the maintenance

and troubleshooting work.

-----------------------------------------------------------------------

230 Volt Input Connection

The Pro-MIG 175 is shipped from the factory connect-
ed for 230 volt input power. If the welder has been
reconnected for 208 volt input power and 230 volt
input is desired, perform the following reconnection
instructions:

1. Disconnect welder from input power and remove

case side panel.

2. Remove lead marked “H3” from CR1 on the control

P.C. Board.

3. Remove tape securing H1 to lead sleeving and

connect H1 to CR1.

4. Insulate unused H3 lead for 300 volts with electri-

cal tape and secure to lead sleeving.

5. Reinstall case side before connecting input power.

208 Volt Input Connection

1. Disconnect welder from input power and remove

case side.

2. Remove lead marked “H1” from CR1 on the control

P.C. Board.

3. Remove tape securing H3 to lead sleeving and

connect H3 to CR1.

4. Insulate unused H1 lead for 300V with electrical

tape and secure to lead sleeving.

WARNING

Grounding

Type 75°C

Wire

Fuse

Wire in Conduit,

Copper

Size

Input

Copper Cond.

Cond.

(Super

Voltage

Hertz

AWG Size

AWG Size

Lag)

208/230

60

8

10

40

WARNING

Pro-MIG 175