Installation, Figure a.1, Warning – Lincoln Electric IM660 RANGER 200 User Manual
Page 15: Connection of ranger 200 to premises wiring, Ranger 200
Advertising

A-7
INSTALLATION
RANGER 200
A-7
Connection of Ranger 200 to premises wiring
must be done by a licensed electrician and must
comply with the National Electrical Code and all
other applicable electrical codes.
240 Volt
60 Hz.
3-Wire
Service
POWER
COMPANY
METER
240 VOLT
120 VOLT
120 VOLT
LOAD
N
NEUTRAL
BUS
GROUND
PREMISES
DISCONNECT AND
SERVICE
OVERCURRENT
PROTECTION
GND
N
NOTE: No. 6 COPPER CONDUCTOR CABLE SEE
NATIONAL ELECTRICAL CODE FOR ALTERNATE WIRE
SIZE RECOMMENDATIONS.
240 VOLT
GROUNDED CONDUCTOR
25AMP
240 VOLT
DOUBLE
POLE
CIRCUIT
BREAKER
DOUBLE POLE DOUBLE THROW
SWITCH RATING TO BE THE SAME
AS OR GREATER THAN PREMISES
SERVICE OVERCURRENT
PROTECTION.
50 AMP, 120/240
VOLT PLUG
NEMA TYPE 14-50
50 AMP, 120/240 VOLT
RECEPTACLE
Figure A.1
CONNECTION OF RANGER 200 TO PREMISES WIRING