Specifications options (details see page 115) – Schaefer Series C/B 1300 User Manual
Page 2

www.schaeferpower.de
Low Power
Converters from 100W to 7.5kW, switchmode
DC / DC Converters, AC / DC Power Supplies & Battery Chargers
AC
or
DC
DC
Input / Output isolation
Continuous short circuit protection
Overvoltage protection with auto restart
Operational from – 40 to +75 °C
Industrial grade components
Compact and robust design
Natural convection
(except for series C56xx and C57xx)
DC Input voltage: 10 - 800V DC
AC Input voltage: 115 / 230V AC,
single phase (with or without PFC) or
200 / 400 / 480V AC, three phases
AC Input frequency: with PFC 47 - 65Hz,
without PFC 47 - 400Hz
Output voltage: 5 / ... / 400V DC
Output current: up to 500A
Output power: 100W - 7.5kW
Features
Input
Voltage range
unit switches off at under- and
overvoltage
No-load input power
5 - 6W typical
except for series 4800, 5600/5700
Inrush current
AC input: limited by thermistor
Hold-up time
AC input: 10ms typical
@ nom. input voltage
(for series 4800: 5ms typical)
Immunity
acc. to EN 61000-6-2
Output
DC output voltages
5
9
12
15
24
28
48
60
110 200 220 400
Line regulation (±10%)
0.1%
Load regulation (10-90%)
0.2%
Load transient (10-90-10%) 6 % typical
Response time to ±1 %
2 - 3 ms
Turn-on rise time
Soft-start, 100 ms typical
Ripple
≤ 1% + 30 mV p-p
Overload protection
current limited to 105-110% of I
nom
Overvoltage protection
OVP switches off module with
automatic return to operation
Remote sense
standard for all series except for
B / BP series; up to 10% of U
nom
for output < 60V DC,
up to 6V for output > 60V DC
General
Efficiency
80 - 92% typical
Operating temperature
-20 to +75°C
(optional: -40 to +75°C)
Load derating
2.5%/°C above + 55°C
Storage temperature
-40 to + 85°C
Cooling
(details see page 131)
= natural convection
= increased air flow recommended
= incl. temperature controlled fans
Humidity
up to 95 % RH, non-condensing
Temperature coefficient
0.02 % / °C typical
Safety / Construction
acc. to EN 60950-1 / EN 50178
Protection category
IP20 acc. to EN 60529,
NEMA or others upon request
EMI
acc. to EN 61000-6-4,
class A, optionally class B
MTBF
100,000 - 140,000h @ 40°C
acc. to MIL - HDBK - 217E (notice 1)
Connectors
(details see page 132)
H15 acc. to DIN 41612
and high current connectors for
I > 50 A,
or terminals / bolts / bars
Specifications
Options (details see page 115)
Input
Inrush current limiting
Reverse polarity protection for DC input
Autoranging for 115 / 230 VAC input
Output
Decoupling diode for redundant / parallel operation
Active current sharing for parallel operation
Remote on / off (inhibit)
Signals
via relay contacts
Power ok (input)
DC ok (output)
Monitoring
of input / output voltage or current via
analog signal
interface card RS232 or CAN Bus (external)
Programming
of output voltage or current via
potentiometer
analog signal
interface card RS232 or CAN Bus (external)
Programming of battery chargers
Temperature compensated charging voltage
Automatic / manual selection of charging characteristic
(external)
Mechanics / environment:
19” sub-rack for eurocassette, refer to page 121
Wall mount
Chassis mount
DIN rail mount
Increased mechanical strength
Tropical protection
Extended temperature range to –40 °C