Converters from 5 to 40kw, switchmode, Specifications, Options (details see page 115) – Schaefer Series C/B 5700 User Manual

Page 2

Advertising
background image

www.schaeferpower.de

Converters from 5 to 40kW, switchmode

Converters from 5 to 40kW, switchmode

High Power

DC / DC Converters, AC / DC Power Supplies & Battery Chargers

■

DC Input voltage: from 80 - 800V DC

■

AC Input voltage: 115 / 230V AC, single phase or

200 / 400 / 480V AC, three phases

■

AC Input frequency: 47 - 400Hz

■

Output voltage: 5 / ... / 800V DC

■

Output current: up to 800A

■

Output power: 5 - 40kW

Specifications

AC

or

DC

DC

■

Input / Output isolation

■

Continuous short circuit protection

■

Overvoltage protection

■

Thermal shutdown with auto-restart

■

Operational from – 40 to +75 °C

■

Industrial grade components

■

High efficiency through ZVS topology

■

High power density

■

Compact and robust design

■

Fan or liquid cooled

Features

Input

Voltage range

narrowing of input voltage range
optimizes the efficiency (pls.
specify); unit switches off at
under- and overvoltage

No-load input power

30W typical

Switch-on time

<1s typical

Inrush current

3-phase AC input: limited by
thermistor (except for

series 55

xx,

64xx, 66xx, 67xx & CW/BW56xx)

Immunity

acc. to EN 61000-6-2

Output

DC output voltages

5

9

12

15

24

28

48

60 110 200 220 400 600 800

Output power

from 5 to 40kW

Line regulation (±10%)

0.1%

Load regulation (10-90%)

0.2%

Load transient (10-90-10%) 6 % typical

Response time to ±1 %

10 ms typical

Turn-on rise time

Soft-start, 300 ms typical

Ripple

≤ 1% + 30 mV p-p

Overload protection

current limited to 105-110% of I

nom

Overvoltage protection

OVP switches off module with
automatic return to operation;
after 5 seconds, the unit will
remain latched off

Remote sense

standard for all series up to 150 V
output, except for battery chargers;
up to 10 % of U

nom

for output < 60

VDC, up to 6 V for output > 60 VDC

General

Efficiency

80 - 95% typical

Operating temperature

-20 to +75°C optional: -40 to +75°C

Load derating

2.5%/°C above + 55°C

Storage temperature

-40 to + 85°C

Cooling
(details see page 131)

= fan cooled
= liquid cooled

Humidity

up to 95 % RH, non-condensing

Temperature coefficient

0.02 % / °C typical

Safety / Construction

acc. to EN 60950-1 / EN 50178

Protection category
(built-in module)

IP20 acc. to EN 60529,
NEMA or others upon request

EMI

acc. to EN 61000-6-4,
class A, optionally class B

MTBF

approx. 70,000h @ 40°C
acc. to MIL - HDBK - 217E (notice 1)

Connectors
(details see page 132)

terminals / bolts / bars
or CombiTacs for Series 5100

Options (details see page 115)

Input

■

Inrush current limiting

■

Reverse polarity protection for DC input

Output

■

Decoupling diode for redundant / parallel operation

■

Active current sharing for parallel operation

■

Remote on / off (inhibit)

■

Reducing of current limiting at high ambient temperature

Signals
via relay contacts

■

Power ok (input)

■

DC ok (output)

Monitoring
of input / output voltage or current via

■

analog signal

■

interface card RS232 or CAN Bus

Programming
of output voltage or current via

■

potentiometer

■

analog signal

■

interface card RS232 or CAN Bus

Programming of battery chargers

■

Temperature compensated charging voltage

■

Automatic / manual selection of charging characteristic

Mechanics / environment:

■

Wall mount

■

Digital or analog V- and A-meter

■

Increased mechanical strength

■

Tropical protection

■

Extended temperature range to –40 °C

Advertising